Application Guide | iC2-Micro Frequency Converters
Bit 02=1: The drive starts the motor with a start command.
Bit 03, No Error/Trip
Bit 03=0: The drive is not in fault mode.
Bit 03=1: The drive trips. To re-establish operation, press
[Reset]
.
Bit 04, No Error/Error (No Trip)
Bit 04=0: The drive is not in fault mode.
Bit 04=1: The drive shows an error but does not trip.
Bit 05, Not Used
Bit 05 is not used in the status word.
Bit 06, No Error/Trip lock
Bit 06=0: The drive is not in fault mode.
Bit 06=1: The drive is tripped and locked.
Bit 07, No Warning/Warning
Bit 07=0: There are no warnings.
Bit 07=1: A warning has occurred.
Bit 08, Speed ≠ Reference/Speed=Reference
Bit 08=0: The motor runs, but the present speed is different from the preset speed reference. It might happen when the speed ramps up/
down during start/stop.
Bit 08=1: The motor speed matches the preset speed reference.
Bit 09, Local Operation/Bus Control
Bit 09=0: [Stop/Reset] is activated on the control unit or
[2] Local
in
P 5.5.3.6 Reference Site
is selected. It is not possible to control the
drive via serial communication.
Bit 09=1: It is possible to control the drive via the fieldbus/serial communication.
Bit 10, Out of Frequency Limit
Bit 10=0: The output frequency has reached the value in
P 5.8.3 Motor Speed Low Limit [Hz]
or
P 5.8.2 Motor Speed High Limit [Hz]
.
Bit 10=1: The output frequency is within the defined limits.
Bit 11, No Operation/In Operation
Bit 11=0: The motor is not running.
Bit 11=1: The drive has a start signal or the output frequency is greater than 0 Hz.
Bit 12, Drive OK/Stopped, Auto Start
Bit 12=0: There is no temporary overtemperature on the drive.
Bit 12=1: The drive stops because of overtemperature but the unit does not trip and resumes operation once the overtemperature
normalizes.
Bit 13, Voltage OK/Limit Exceeded
Danfoss A/S © 2024.03 AB413939445838en-000301 / 130R1254 |