Application Guide | iC2-Micro Frequency Converters
e3
0b
a0
92
.1
0
E19E
0000
0000
03E8
H
H
H
H
PKE
IND
PWE
PWEhigh
low
Figure 61: Telegram
NOTICE
P 5.8.2 Motor Speed High Limit [Hz]
is a single word, and the parameter command for write in EEPROM is E.
P 5.8.2 Motor Speed
High Limit [Hz]
is 19E in hexadecimal. The parameter number is 414.
The response from the follower to the master is shown in the
e3
0b
a0
93
.1
0
119E
0000
0000
03E8
H
H
H
H
PKE
IND
PWE
PWEhigh
low
Figure 62: Response from Master
6.1.6.3.3
Reading a Parameter Value
Read the value in
P 5.5.4.2 Ramp 1 Ramp Up Time
.
PKE = 1155 hex - Read parameter value in
P 5.5.4.2 Ramp 1 Ramp Up Time
. The parameter number is 341.
l
IND = 0000 hex.
l
PWE
HIGH
= 0000 hex.
l
PWE
LOW
= 0000 hex.
e3
0b
a0
94
.1
0
1155
0000
0000
0000
H
H
H
H
PKE
IND
PWE
PWEhigh
low
Figure 63: Telegram
If the value in
P 5.5.4.2 Ramp 1 Ramp Up Time
is 10 s, the response from the follower to the master is shown in the
.
e3
0b
a2
67
.1
0
1155
0000
0000
03E8
H
H
H
H
PKE
IND
PWE
PWEhigh
low
Figure 64: Response
3E8 hex corresponds to 1000 decimal. The conversion index for
P 5.5.4.2 Ramp 1 Ramp Up Time
is -2, that is, 0.01.
P 5.5.4.2 Ramp 1 Ramp Up Time
is of the type Unsigned 32. The parameter number is 341.
6.1.7
Modbus RTU
6.1.7.1
Modbus RTU Introduction
Prerequisite knowledge
Danfoss A/S © 2024.03 AB413939445838en-000301 / 130R1254 |