Set the reference value to correspond to the minimum position of the control panel potentiometer.
Default value:
0.000
Parameter type:
Range (-4999.000–4999.000)
Parameter
Number
681
Unit:
–
Data type:
int32
Access type:
Read/Write
7.9.3.5
Live Zero (Menu Index 9.5.6)
P 9.5.6.1 Live Zero Response
Enter the timeout time. The function set in
P 9.5.6.2 Live Zero Timeout Function
is activated when the input signal on terminal is below
50% of the minimal value (for example, the minimal value for Terminal 33 voltage mode is
P 9.5.2.3 T33 Low Voltage
) for a time period
defined in the parameter.
Default value:
10
Parameter type:
Range (1–99)
Parameter
Number
600
Unit:
s
Data type:
uint8
Access type:
Read/Write
P 9.5.6.2 Live Zero Timeout Function
Select the timeout function. The function set in the parameter is activated when the input signal on terminal is below 50% of the
minimal value (for example, the minimal value for Terminal 33 voltage mode is
P 9.5.2.3 T33 Low Voltage
) for a time period defined in
P
9.5.6.1 Live Zero Response
.
Default value:
0 [Off]
Parameter type
Selection
Parameter
Number
601
Unit:
–
Data type:
enum
Access type:
Read/Write
The following are the selections for the parameter.
Selection number
Selection name
0
Off
1
Freeze Output
2
Stop
3
Jogging
4
Max Speed
5
Stop and Trip
256
| Danfoss A/S © 2024.03 AB413939445838en-000301 / 130R1254
Application Guide | iC2-Micro Frequency Converters