Application Guide | iC2-Micro Frequency Converters
6.2
How to Control the Drive
6.2.1
Introduction
This section describes codes which can be used in the function and data fields of a Modbus RTU telegram.
6.2.2
Function Codes Supported by Modbus RTU
Modbus RTU supports use of the following function codes in the function field of a telegram:
Table 57: Function Codes
Function
Function code (hex)
Read coils
1
Read holding registers
3
Write single coil
5
Write single register
6
Write multiple coils
F
Write multiple registers
10
Get comm. event counter
B
Report follower ID
11
Read write multiple registers
17
Table 58: Function Codes
Function
Function code
Subfunction code
Subfunction
1
Restart communication.
2
Return diagnostic register.
10
Clear counters and diagnostic
register.
11
Return bus message count.
12
Return bus communication er-
ror count.
13
Return follower error count.
Diagnostics
8
14
Return follower message
count.
6.2.3
Modbus Exception Codes
For a full explanation of the structure of an exception code response, refer to
.
Danfoss A/S © 2024.03 AB413939445838en-000301 / 130R1254 |
103