Application Guide | iC2-Micro Frequency Converters
2.
To test motor operation, start the motor at low speed (100–200 RPM). If the motor does not turn, check installation, general
parameter configurations, and motor data.
3.
Perform parking operation by setting
P 5.6.14 Sync. Motor Parking Current %
and
P 5.6.13 Sync. Motor Parking Time
. The
factory setting values of the parameters can be adjusted and increased for applications with high inertia. Start the motor at
nominal speed. If the application does not run well, check the VVC+ PM settings. The following table shows recommendations
in different applications.
Table 13: Recommendations in Different Applications
Application
Settings
Low inertia applications ILoad/IMotor<5
• Increase the value for
P 4.4.4.10 Voltage filter time const
.
by factor 5–10.
• Reduce the value for
P 4.4.4.7 Damping Gain
.
• Reduce the value (<100%) for
P 4.4.4.14 Min. Current at
Low Speed
.
Medium inertia applications 50>ILoad/IMotor>5
Keep calculated values.
High inertia applications ILoad/IMotor>50
Increase the values for
P 4.4.4.7 Damping Gain
,
P 4.4.4.9 Low
Speed Filter Time Const.
, and
P 4.4.4.8 High Speed Filter Time
Const
.
High load at low speed <30% (rated speed)
Increase the value for
P 4.4.4.10 Voltage filter time const
.
Increase the value for
P 4.4.4.14 Min. Current at Low Speed
(>100% for longer time can overheat the motor).
If the motor starts oscillating at a certain speed, increase
P 4.4.4.7 Damping Gain
. Increase the value in small steps. Starting
torque can be adjusted in
P 4.4.4.14 Min. Current at Low Speed
. 100% provides nominal torque as starting torque.
5.4.4
Speed Control Configuration with I/O Using Default
1.
Go to
parameter group 5
and specify the following:
Parameter index
Parameter name
Recommended settings
Parameter number
5.4.3
Motor Control Principle
Use default:
[1] VVC+
. In most situations,
selecting VVC+ provides optimum
performance without further adjustments.
101
5.4.2
Operation Mode
Use default:
[0] Speed Open Loop
100
9.4.1.2
T13 Digital Input
Use default:
[8] Start
510
9.4.1.3
T14 Digital Input
Use default:
[10] Reversing
511
9.4.1.4
T15 Digital Input
Use default:
[1] Reset
512
9.4.1.5
T17 Digital Input
Use default:
[14] Jog
513
5.5.3.7
Reference 1 Source
[1] Analog Input 33
315
9.5.1.2
T31 Analog Output
Use default:
[100] Output Frequency
691
9.4.3.1
Function Relay
Use default:
[9] Fault
540
5.5.3.3
Reference Maximum
Use default: 50
303
Danfoss A/S © 2024.03 AB413939445838en-000301 / 130R1254 |
53
Содержание iC2
Страница 1: ...iC2 Micro Frequency Converters Application Guide drives danfoss com...
Страница 2: ......
Страница 10: ...10 Danfoss A S 2024 03 AB413939445838en 000301 130R1254 Application Guide iC2 Micro Frequency Converters...
Страница 290: ...290 Danfoss A S 2024 03 AB413939445838en 000301 130R1254 Application Guide iC2 Micro Frequency Converters...
Страница 291: ......