Application Guide | iC2-Micro Frequency Converters
Use this parameter to select whether the drive setup selection is controlled via the terminals (digital input) and/or via the fieldbus.
NOTICE
This parameter is active only when
P 5.5.1.1 Control Place Selection
is set to
[0] Digital and control word
.
Default value:
3 [Logic OR]
Parameter type:
Selection
Parameter
number:
855
Unit:
–
Data type:
enum
Access type:
Read/Write
The following are the selections for the parameter.
Selection number
Selection name
Selection description
0
Digital input
A digital input triggers the setup selection.
1
Bus
A serial communication port or the fieldbus triggers the setup
selection.
2
Logic AND
The fieldbus/serial communication port and a digital input
trigger the setup selection.
3
Logic OR
The fieldbus/serial communication port or a digital input triggers
the setup selection.
P 5.5.2.7 Preset Reference Select
Use this parameter to select whether the drive Preset Reference selection is controlled via the terminals (digital input) and/or via the
fieldbus.
NOTICE
This parameter is active only when
P 5.5.1.1 Control Place Selection
is set to
[0] Digital and control word
.
Default value:
3 [Logic OR]
Parameter type:
Selection
Parameter
number:
856
Unit:
–
Data type:
enum
Access type:
Read/Write
The following are the selections for the parameter.
Selection number
Selection name
Selection description
0
Digital input
A digital input triggers the preset reference selection.
1
Bus
A serial communication port or the fieldbus triggers the preset
reference selection.
Danfoss A/S © 2024.03 AB413939445838en-000301 / 130R1254 |
155