Selection number
Selection name
Selection description
0
Rotor Detection
Estimates the electrical angle of the rotor and uses that as a
starting point. This is the standard selection for automation drive
applications. If flying start detects that the motor is running at
low speed or is stopped, the drive can detect the rotor position
(the angle), and start the motor from there.
1
Parking
The Parking function applies DC current across the stator
winding and rotates the rotor to electrical zero position. This
selection is typically selected for pump and fan applications. If
flying start detects that the motor is running at low speed or is
stopped, the drive sends out a DC current to make the motor
park at an angle and then start the motor from.
3
Rotor Last Position
This option takes the advantage of the last position of rotor at
stop and gives a quick start. It is only used in the situation of
controlled stop, the drive records the last position of rotor at stop
and starts the motor directly without rotor detection and angle
calculation. When in the situation of non-controlled stop and
power cycle, the drive needs to detect the rotor position. This
option can be used for fast restart application. Start may fail if the
rotor position has been changed.
P 5.6.12 Sync. Motor Detection Current %
Use this parameter to adjust the amplitude of the test pulse during position detection at start. Adjust this parameter to improve the
position measurement.
Default value:
100
Parameter type:
Range (Size Related)
Parameter
number:
146
Unit:
%
Data type:
uint16
Access type:
Read/Write
P 5.6.13 Sync. Motor Parking Time
Use this parameter to set the duration of the Parking Current set in
P 5.6.14 Sync. Motor Parking Current %
, once activated.
Default value:
3.0
Parameter type:
Range (0.1–60.0)
Parameter
number:
207
Unit:
s
Data type:
uint16
Access type:
Read/Write
P 5.6.14 Sync. Motor Parking Current %
Use this parameter to set current as percentage of the rated motor current, set with
P 4.2.2.3 Nominal Current
. Is used when
[1] Parking
is
selected in
P 5.6.11 Sync. Motor Start Mode
.
Default value:
100
Parameter type:
Range (0–150)
Parameter
number:
206
Unit:
%
168
| Danfoss A/S © 2024.03 AB413939445838en-000301 / 130R1254
Application Guide | iC2-Micro Frequency Converters
Содержание iC2
Страница 1: ...iC2 Micro Frequency Converters Application Guide drives danfoss com...
Страница 2: ......
Страница 10: ...10 Danfoss A S 2024 03 AB413939445838en 000301 130R1254 Application Guide iC2 Micro Frequency Converters...
Страница 290: ...290 Danfoss A S 2024 03 AB413939445838en 000301 130R1254 Application Guide iC2 Micro Frequency Converters...
Страница 291: ......