Application Guide | iC2-Micro Frequency Converters
6.1.6.2.7
The PKE Field
The PKE field contains 2 subfields:
l
Parameter command and response (AK)
l
Parameter number (PNU)
15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0
e3
0b
b
91
8.
10
PKE
IND
PWE
high
PWE
low
AK
PNU
Pa
ra
m
et
er
co
m
m
an
ds
an
d
re
p
lie
s
Pa
ra
m
et
er
nu
m
b
er
Figure 60: PKE Field
Bits 12–15 transfer parameter commands from master to follower and return processed follower responses to the master.
Table 25: Parameter Commands
Parameter commands master->follower
Bit number
Parameter command
15
14
13
12
0
0
0
0
No command.
0
0
0
1
Read parameter value.
0
0
1
0
Write parameter value in RAM (word).
0
0
1
1
Write parameter value in RAM (double word).
1
1
0
1
Write parameter value in RAM and EEPROM (double word).
1
1
1
0
Write parameter value in RAM and EEPROM (word).
1
1
1
1
Read text.
Table 26: Response
Response follower->master
Bit number
Response
15
14
13
12
0
0
0
0
No response.
0
0
0
1
Parameter value transferred (word).
0
0
1
0
Parameter value transferred (double word).
Danfoss A/S © 2024.03 AB413939445838en-000301 / 130R1254 |
79
Содержание iC2
Страница 1: ...iC2 Micro Frequency Converters Application Guide drives danfoss com...
Страница 2: ......
Страница 10: ...10 Danfoss A S 2024 03 AB413939445838en 000301 130R1254 Application Guide iC2 Micro Frequency Converters...
Страница 290: ...290 Danfoss A S 2024 03 AB413939445838en 000301 130R1254 Application Guide iC2 Micro Frequency Converters...
Страница 291: ......