Application Guide | iC2-Micro Frequency Converters
Selection number
Selection name
Selection description
45
Latched Start Reverse
The motor starts to run reverse when a pulse is applied for
minimum 4 ms. The motor stops when stop commands are
given.
51
External Interlock
This function makes it possible to give an external fault to
the frequency converter. This fault is treated as an internally
generated alarm.
60
Counter A (up)
Input for increment counting in the SLC counter A.
61
Counter A (down)
Input for decrement counting in the SLC counter A.
62
Reset Counter A
Input for reset of counter A.
63
Counter B (up)
Input for increment counting in the SLC counter B.
64
Counter B (down)
Input for decrement counting in the SLC counter B.
65
Reset Counter B
Input for reset of counter B.
101
Sleep
A signal applied puts the frequency converter into sleep mode.
P 9.4.1.5 T17 Digital Input
Select the function from the available digital input range.
Default value:
14 [Jog]
Parameter type:
Selection
Parameter
number:
513
Unit:
–
Data type:
enum
Access type:
Read/Write
The following are the selections for the parameter.
Selection number
Selection name
Selection description
0
No Operation
No reaction to signals transmitted to the terminal.
1
Reset
Resets the frequency converter after a trip/alarm. Not all alarms
can be reset.
2
Coast Inverse
Coasting stop, inverted input (NC). The frequency converter
leaves the motor in free mode. Logic 0
⇒
coasting stop.
3
Coast and Reset Inverse
Reset and coasting stop inverted input (NC). Leaves motor in free
mode and resets frequency converter. Logic 0
⇒
coasting stop.
Logic 1 to Logic 0
⇒
reset.
4
Quick Stop Inverse
Inverted input (NC). Generates a stop in accordance with the
quick stop ramp time set in
P 5.7.7 Quick Stop Ramp Time
. When
the motor stops, the shaft is in free mode. Logic 0
⇒
Quick-stop.
Note:
When the frequency converter is at the torque limit and
has received a stop command, it may not stop by itself. To ensure
that the frequency converter stops, configure a digital output to
[27] Torque limit
and stop and connect this digital output to a
digital input that is configured as coast.
Danfoss A/S © 2024.03 AB413939445838en-000301 / 130R1254 |
229