Use this parameter to select the function of the
Stop/Reset
button. To avoid accidental stop or reset of the drive from control panel, select
[0] Disabled
. The setting can be locked by
P 6.6.20 Password
.
Default value:
1 [Enabled]
Parameter type:
Selection
Parameter
number:
44
Unit:
–
Data type:
enum
Access type:
Read/Write
The following are the selections for the parameter.
Selection number
Selection name
0
Disabled
1
Enabled
7
Reset Only Enabled
7.6.4.2
Digital/Bus (Menu Index 5.5.2)
P 5.5.2.1 Coasting Select
Use this parameter to select whether the coasting function is controlled via the terminals (digital input) and/or via the bus.
NOTICE
This parameter is active only when
P 5.5.1.1 Control Place Selection
is set to
[0] Digital and control word
.
Default value:
3 [Logic OR]
Parameter type:
Selection
Parameter
number:
850
Unit:
–
Data type:
enum
Access type:
Read/Write
The following are the selections for the parameter.
Selection number
Selection name
Selection description
0
Digital input
Activate the coasting command via a digital input
1
Bus
Activate the coasting command via the serial communication
port or fieldbus option.
2
Logic AND
Activate the coasting command via the fieldbus/serial
communication port and 1 extra digital input.
3
Logic OR
Activate the coasting command via the fieldbus/serial
communication port or via 1 of the digital inputs.
P 5.5.2.2 Quick Stop Select
Use this parameter to select whether the Quick Stop function is controlled via the terminals (digital input) and/or via the bus.
152
| Danfoss A/S © 2024.03 AB413939445838en-000301 / 130R1254
Application Guide | iC2-Micro Frequency Converters