Application Guide | iC2-Micro Frequency Converters
Selection number
Selection name
Selection description
15
Preset Reference On
Shift between external reference and preset reference. It is
assumed that
[1] External/preset
has been selected in
P 5.5.3.5
Reference Function
. Logic 0 = external reference active; logic 1=1
of the 8 preset references is active.
16
Preset Ref. Bit 0
Preset reference bits 0, 1, and 2 enable the selection of 1 of the 8
preset references. See
17
Preset Ref. Bit 1
Preset reference bits 0, 1, and 2 enable the selection of 1 of the 8
preset references. See
18
Preset Ref. Bit 2
Preset reference bits 0, 1, and 2 enable the selection of 1 of the 8
preset references. See
19
Freeze Reference
Freeze the actual reference, which is now the point of enable/
condition for
[21] Speed up
and
[22] Speed down
to be used.
If
[21] Speed up
or
[22] Speed down
is used, the speed change
always follows ramp 2 (
P 5.5.4.9 Ramp 2 Accel. Time
and
P
5.5.4.10 Ramp 2 Decel. Time
) in the range 0–
P 5.5.3.3 Reference
Maximum
.
20
Freeze Output
Freeze the actual motor frequency (Hz), which is now the point
of enable/condition for
[21] Speed up
and
[22] Speed down
to
be used. If
[21] Speed up
or
[22] Speed down
is used, the speed
change always follows ramp 2 (
P 5.5.4.9 Ramp 2 Accel. Time
and
P 5.5.4.10 Ramp 2 Decel. Time
) in the range 0–
P 4.2.2.4 Nominal
Frequency
.
Note:
When
[20] Freeze output
is active, the frequency converter
cannot be stopped by setting the signal on
[8] Start to low
.
Stop the frequency converter via a terminal programmed for
[2]
Coasting inverse
or
[3] Coast and reset, inverse
.
21
Speed Up
Select
[21] Speed up
and
[22] Speed down
if digital control of
the up/down speed is needed (motor potentiometer). Activate
this function by selecting either
[19] Freeze reference
or
[20]
Freeze output
. When speed up/down is activated for less than
400 ms, the resulting reference is increased/decreased by 0.1%. If
speed up/down is activated for more than 400 ms, the resulting
reference follows the setting in ramping up/down
P 5.5.4.9 Ramp
2 Accel. Time
/
P 5.5.4.10 Ramp 2 Decel. Time
22
Speed Down
Select
[21] Speed up
and
[22] Speed down
if digital control of
the up/down speed is needed (motor potentiometer). Activate
this function by selecting either
[19] Freeze reference
or
[20]
Freeze output
. When speed up/down is activated for less than
400 ms, the resulting reference is increased/decreased by 0.1%. If
speed up/down is activated for more than 400 ms, the resulting
reference follows the setting in ramping up/down
P 5.5.4.9 Ramp
2 Accel. Time
/
P 5.5.4.10 Ramp 2 Decel. Time
23
Set-up Select Bit 0
Select
[23] Set-up select bit 0
to select 1 of the 2 set-ups. Set
P
6.6.1 Active Set-up
to
[9] Multi Set-up
.
25
Start and Coast
Select
[25] Start and Coast
for a start command or coast stop.
Logic 1=start, logic 0=coast stop.
Danfoss A/S © 2024.03 AB413939445838en-000301 / 130R1254 |
225
Содержание iC2
Страница 1: ...iC2 Micro Frequency Converters Application Guide drives danfoss com...
Страница 2: ......
Страница 10: ...10 Danfoss A S 2024 03 AB413939445838en 000301 130R1254 Application Guide iC2 Micro Frequency Converters...
Страница 290: ...290 Danfoss A S 2024 03 AB413939445838en 000301 130R1254 Application Guide iC2 Micro Frequency Converters...
Страница 291: ......