Parameter index
Parameter name
Example setting
Parameter number
5.5.3.9
Reference 3 Source
[11] Local Bus Reference
317
5.5.2.1
Coasting Select
[3] Logic OR
850
5.5.2.2
Quick Stop Select
[3] Logic OR
851
5.5.2.4
Start Select
[3] Logic OR
853
5.5.2.5
Reversing Select
[3] Logic OR
854
9.4.1.2
T13 Digital Input
[8] Start
510
9.4.1.3
T14 Digital Input
[10] Reversing
511
9.4.1.4
T15 Digital Input
[1] Reset
512
9.4.1.5
T17 Digital Input
[14] Jog
513
5.3
Setting up the Drive using Quick Access via Control Panel
The following steps shows the quick access setup.
1.
Power up the drive.
2.
Press
Home/Menu
button on the control panel for accessing the menu structure.
3.
Select
QACC
, and enter
q1 Motor Data
to first select motor type using
P 4.2.1.1 Motor Type
.
4.
Set the value of motor data parameters, in sequence, based on the selected motor type.
5.
Execute Automatic Motor Adaptation (AMA), if needed. See
5.4.5 Automatic Motor Adaptation (AMA)
.
6.
Select application type in
q2 Application Selection
and wiring I/O terminals accordingly. For more information, see
Application Selection Overview
.
7.
Enter
q3 Motor Control
to configure reference limitations, output limitations, and ramp time.
8.
Press
REM/LOC
, to set the drive in remote operation.
9.
To start the drive by I/O terminals.
5.4
Motor Configuration
5.4.1
Motor Configuration Overview
The setup examples in this chapter describe motor configuration.
NOTICE
The parameters specified in motor configuration, cannot be adjusted when the motor is running.
The configuration setup contains, menu index, parameter name, recommended parameter setting, and parameter number. The
parameter number is a unique identification reference for the parameter. For detailed description on a parameter, refer
Chapter
Parameter Descriptions
.
5.4.2
Asynchronous Motor Setup
1.
For asynchronous motor setup, set the following parameters:
50
| Danfoss A/S © 2024.03 AB413939445838en-000301 / 130R1254
Application Guide | iC2-Micro Frequency Converters