6.1.6.2.4
Drive Address (ADR)
Address format 1–126:
l
Bit 7 = 1 (address format 1–126 active).
l
Bit 0–6 = drive address 1–126.
l
Bit 0–6 = 0 broadcast.
The follower returns the address byte unchanged to the master in the response telegram.
6.1.6.2.5
Data Control Byte (BCC)
The checksum is calculated as an XOR-function. Before the first byte in the telegram is received, the calculated checksum is 0.
6.1.6.2.6
The Data Field
The structure of data blocks depends on the type of telegram. There are 3 telegram types, and the type applies for both control
telegrams (master->follower) and response telegrams (follower->master).
The 3 types of telegram are:
l
Process block (PCD).
l
Parameter block.
l
Text block.
Process block (PCD)
The PCD is made up of a data block of 4 bytes (2 words) and contains:
l
Control word and reference value (from master to follower).
l
Status word and present output frequency (from follower to master).
STX
LGE
ADR
PCD1
PCD2
BCC
e3
0b
a2
69
.1
0
Figure 57: Process Block
Parameter block
The parameter block is used to transfer parameters between master and follower. The data block is made up of 12 bytes (6 words) and
also contains the process block.
e3
0b
a2
71
.1
0
STX
LGE
ADR
PCD1
PCD2
BCC
PKE
IND
PWE
PWEhigh
low
Figure 58: Parameter Block
Text block
The text block is used to read or write texts via the data block.
e3
0b
a2
70
.1
0
STX
LGE
ADR
PCD1
PCD2
BCC
PKE
IND
Ch1
Ch2
Chn
Figure 59: Text Block
78
| Danfoss A/S © 2024.03 AB413939445838en-000301 / 130R1254
Application Guide | iC2-Micro Frequency Converters
Содержание iC2
Страница 1: ...iC2 Micro Frequency Converters Application Guide drives danfoss com...
Страница 2: ......
Страница 10: ...10 Danfoss A S 2024 03 AB413939445838en 000301 130R1254 Application Guide iC2 Micro Frequency Converters...
Страница 290: ...290 Danfoss A S 2024 03 AB413939445838en 000301 130R1254 Application Guide iC2 Micro Frequency Converters...
Страница 291: ......