background image

   

Industrial

 

Electronic Devices 

 

 

 ADFweb.com Srl – IT31010 – Mareno – Treviso                                                      INFO:  

www.adfweb.com

      Phone +39.0438.30.91.31            

 

User Manual   

PROFINET Master / EtherNet/IP 

 

Document code: MN67B78_ENG     Revision 1.000    Page 1 of 28

 

 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

 

 
 
 
 
 

 

User Manual 

Revision 1.000 
English 

 

PROFINET Master / EtherNet/IP - 
Converter

 

 

(Order Code: HD67B78-A1) 

 

for Website information:  

http://www.adfweb.com/?Product=HD67B78

    

 

for Price information: 

http://www.adfweb.com/?Price=HD67B78-A1

  

 
 

Benefits and Main Features: 

 

Triple electrical isolation 

 

Two Ethernet ports 

 

Temperature range: -40°C/+85°C (-40°F/+185°F) 

 

For others PROFINET Master devices, see also the following links:  

 
PROFINET Master from/to …

 

www.adfweb.com?Product=HD67B45

  

(

OPC UA Server

www.adfweb.com?Product=HD67B70

  

(

Serial

www.adfweb.com?Product=HD67B71

  

(

Modbus Slave

www.adfweb.com?Product=HD67B72

  

(

PROFIBUS Slave

www.adfweb.com?Product=HD67B73

  

(

CAN

www.adfweb.com?Product=HD67B74

  

(

CANopen

www.adfweb.com?Product=HD67B75

  

(

DeviceNet Slave

www.adfweb.com?Product=HD67B76

  

(

Modbus TCP Slave

www.adfweb.com?Product=HD67B77

  

(

SNMP Agent

www.adfweb.com?Product=HD67B79

  

(

KNX

www.adfweb.com?Product=HD67B80

    

(

MQTT

www.adfweb.com?Product=HD67B81

    

(

BACnet Slave

www.adfweb.com?Product=HD67B82

    

(

IEC 61850 Server

www.adfweb.com?Product=HD67B84

  

(

Ethernet

 
Do you have an your customer protocol? 

See the following links: 

www.adfweb.com?Product=HD67003

 

 
Do you need to choose a device? do you want help? 

Ask it to the following link: 

www.adfweb.com?Cmd=helpme

 

User Manual 

Summary of Contents for HD67B78-A1

Page 1: ...aster from to www adfweb com Product HD67B45 OPC UA Server www adfweb com Product HD67B70 Serial www adfweb com Product HD67B71 Modbus Slave www adfweb com Product HD67B72 PROFIBUS Slave www adfweb com Product HD67B73 CAN www adfweb com Product HD67B74 CANopen www adfweb com Product HD67B75 DeviceNet Slave www adfweb com Product HD67B76 Modbus TCP Slave www adfweb com Product HD67B77 SNMP Agent ww...

Page 2: ... AND TECHNICAL SUPPORT 28 RETURN POLICY 28 Pagina 2 di 28 UPDATED DOCUMENTATION Dear customer we thank you for your attention and we remind you that you need to check that the following document is Updated Related to the product you own To obtain the most recently updated document note the document code that appears at the top right hand corner of each page of this document With this Document Code...

Page 3: ...locks etc QUALIFIED PERSONNEL The device can be used only by qualified personnel strictly in accordance with the specifications Qualified personnel are persons who are familiar with the installation assembly commissioning and operation of this equipment and who have appropriate qualifications for their job RESIDUAL RISKS The device is state of the art and is safe The instruments can represent a po...

Page 4: ...lectronic Devices ADFweb com Srl IT31010 Mareno Treviso INFO www adfweb com Phone 39 0438 30 91 31 User Manual PROFINET Master EtherNet IP Document code MN67B78_ENG Revision 1 000 Page 4 of 28 EXAMPLE OF CONNECTION ...

Page 5: ...DFweb com Srl IT31010 Mareno Treviso INFO www adfweb com Phone 39 0438 30 91 31 User Manual PROFINET Master EtherNet IP Document code MN67B78_ENG Revision 1 000 Page 5 of 28 CONNECTION SCHEME Figure 1 Connection scheme for HD67B78 A1 ...

Page 6: ...characteristics Up to 496 bytes in reading and 496 bytes in writing Two directional information between EtherNet IP and PROFINET Mountable on 35mm Rail DIN Wide power supply input range 8 24V AC or 12 35V DC Wide temperature range 40 C 85 C 40 F 185 F CONFIGURATION You need Compositor SW67B78 software on your PC in order to perform the following Define the parameter of the PROFINET Define the para...

Page 7: ...ster EtherNet IP Document code MN67B78_ENG Revision 1 000 Page 7 of 28 POWER SUPPLY The devices can be powered between a wide range of tensions For more details see the two tables below VAC VDC Vmin Vmax Vmin Vmax HD67B78 A1 8V 24V 12V 35V Consumption at 24V DC Device W VA HD67B78 A1 4 Caution Not reverse the polarity power HD67B78 A1 ...

Page 8: ...e device has got two functions mode depending of the position of the Dip1 of Dip Switch A The first with Dip1 in Off position factory setting is used for the normal working of the device The second with Dip1 in On position is used for upload the Project Firmware For the operations to follow for the updating see UPDATE DEVICE section According to the functioning mode the LEDs will have specifics fu...

Page 9: ... slowly 0 5Hz update in progress 3 BF bus fault red ON The Ethernet connection is defective the IP address exists several times in the network the own NameOfStation exists several times in the network no IP address has been set Flashing At least one configured AR is no longer in the data exchange OFF No errors are present Blinks quickly Boot state Blinks very slowly 0 5Hz update in progress 4 SF g...

Page 10: ... Ethernet connection must be made using Connector3 or Connector4 of HD67B78 A1 with at least a Category 5E cable The maximum length of the cable should not exceed 100m The cable has to conform to the T568 norms relative to connections in cat 5 up to 100 Mbps To connect the device to an Hub Switch is recommended the use of a straight cable to connect the device to a PC PLC other is recommended the ...

Page 11: ...ter use the available software that runs with Windows called SW67B78 It is downloadable on the site www adfweb com and its operation is described in this document This manual is referenced to the last version of the software present on our web site The software works with MSWindows XP Vista Seven 8 10 32 64bit When launching the SW67B78 the window below appears Fig 2 Note It is necessary to have i...

Page 12: ...contains the entire device s configuration A device s configuration can also be imported or exported To clone the configurations of a programmable PROFINET Master EtherNet IP Converter in order to configure another device in the same manner it is necessary to maintain the folder and all its contents To clone a project in order to obtain a different version of the project it is sufficient to duplic...

Page 13: ...there is the possibility to change the language of the software and check the updatings for the compositor In the section Language it is possible to change the language of the software In the section Connection Options it is possible to check if there are some updatings of the software compositor in ADFweb com website Checking the option Check Software Update at Start of Program the SW67B78 check ...

Page 14: ...9 0438 30 91 31 User Manual PROFINET Master EtherNet IP Document code MN67B78_ENG Revision 1 000 Page 14 of 28 In the section Software Settings it is possible to enable disable some keyboard s commands for an easier navigation inside the tables contained in the different sections of the software ...

Page 15: ...lt gateway of the net is defined This feature can be enabled or disabled pressing the Check Box field This feature is used for going out of the net In the field Name of Station the name of the PROFINET node is defined In the field IP Address the IP address for EtherNet IP side of the converter is defined In the field SubNet Mask the SubNet Mask for EtherNet IP side of the converter is defined In t...

Page 16: ...ices Present in Network window PROFINET ACCESS By Pressing the PROFINET Access button from the main window for SW67B78 Fig 2 the window Definition of PROFINET Devices Present in Network appears Fig 4 This section is used to define the list of the PROFINET slaves to read write with the PROFINET Master It is possible to add the PROFINET slaves from the hardware catalog If a new device will be connec...

Page 17: ...ame of Station is checked the name of the PROFINET slave is defined In the field IP Address the IP Address of the PROFINET slave is defined In the field Update Time ms the delay used for IO communication is defined In the field Answer TimeOut the allowed number of cycles without response from the slave is defined Warning The data from to the slaves are mapped consecutively into the IN OUT PROFINET...

Page 18: ...Device appears Fig 5 In the main table it is possible to import the Modules of the PROFINET device in use In the properties below it is possible to set the parameters of the slave These options depends on the slave in use refer to the manual of the PROFINET device The means of the checkboxes inside the table are If the field Map Only Data is checked only the data of the modules are mapped into the...

Page 19: ...Turn ON the device Connect the Ethernet cable Insert the IP 192 168 2 205 Select which operations you want to do Press the Execute update firmware button to start the upload When all the operations are OK turn OFF the Device Put Dip2 of Dip Switch A in OFF position Turn ON the device If you know the actual IP address of the device you have to use this procedure Turn ON the Device with the Ethernet...

Page 20: ...he updating Try with another PC Try to restart the PC Check the LAN settings If you are using the program inside a Virtual Machine try to use in the main Operating System If you are using Windows Seven Vista 8 or 10 make sure that you have the administrator privileges In case you have to program more than one device using the UDP Update you have to cancel the ARP table every time you connect a new...

Page 21: ...GURATION The configuration and commissioning of the EtherNet IP Converter as described on the following pages was accomplished with the help of the RSLogix 5000 software of Rockwell Automation In case of using a control system from another supplier please attend to the associated documentation These are the steps to follow 1 Create a Generic Ethernet Module under the Ethernet section in the I O Co...

Page 22: ...T shall be selected as the data type The HD67B78 A1 can uses up to 244 bytes for input assembly instance 101 and 244 bytes for output assembly instance 100 RSLogix 5000 requires a configuration assembly instance Both modules do not provide a configuration assembly instance Therefore it is allowed to select an instance of 3 and to set the value to zero 3 The setting of 10msec for the Requested Pack...

Page 23: ...com Srl IT31010 Mareno Treviso INFO www adfweb com Phone 39 0438 30 91 31 User Manual PROFINET Master EtherNet IP Document code MN67B78_ENG Revision 1 000 Page 23 of 28 4 After the configuration is completed the controller tags are created ...

Page 24: ...91 31 User Manual PROFINET Master EtherNet IP Document code MN67B78_ENG Revision 1 000 Page 24 of 28 5 With RSLinks Classic Lite after have done a network scan RSWho and finding the EtherNet IP device it is possible to load the EDS file for the device in order to have the Module Info compiled Before After ...

Page 25: ...m Srl IT31010 Mareno Treviso INFO www adfweb com Phone 39 0438 30 91 31 User Manual PROFINET Master EtherNet IP Document code MN67B78_ENG Revision 1 000 Page 25 of 28 MECHANICAL DIMENSIONS Figure 8 Mechanical dimensions scheme for HD67B78 A1 ...

Page 26: ...ring part number is formed by a valid combination of the following HD67B78 A 1 Connectors Type 1 Removable 5mm Screw Terminal Enclosure Type A 1M 35mm DIN Rail mounting Device Family HD67B78 PROFINET Master EtherNet IP Converter Order Code HD67B78 A1 PROFINET Master EtherNet IP Converter ACCESSORIES Order Code AC34011 Rail DIN Power Supply 220 240V AC 50 60Hz 12 V DC Order Code AC34012 Rail DIN Po...

Page 27: ...ean countries with separate collection systems This symbol on the product or on its packaging indicates that this product may not be treated as household rubbish Instead it should be taken to an applicable collection point for the recycling of electrical and electronic equipment If the product is disposed correctly you will help prevent potential negative environmental factors and impact of human ...

Page 28: ...sh to exchange or repair it please do the following Obtain a Product Return Number PRN from our internet support at www adfweb com Together with the request you need to provide detailed information about the problem Send the product to the address provided with the PRN having prepaid the shipping costs shipment costs billed to us will not be accepted If the product is within the warranty of twelve...

Reviews: