Application Guide | iC2-Micro Frequency Converters
Table 71: Warning and Fault Events Summary
(continued)
Number
Description
Warning
Fault
Trip
lock
Cause
26
Brake Overload
X
X
–
The power transmitted to the brake resistor over the last 120 s
exceeds the limit. Possible corrections: Decrease brake energy
via lower speed or longer ramp time.
27
Brake IGBT/Brake
chopper Short Cir-
cuited
–
X
X
Brake transistor is short-circuited, thus brake function is dis-
connected.
28
Brake Check
–
X
X
Brake resistor is not connected/working.
30
U phase loss
–
X
X
Motor phase U is missing. Check the phase.
31
V phase loss
–
X
X
Motor phase V is missing. Check the phase.
32
W phase loss
–
X
X
Motor phase W is missing. Check the phase.
36
Mains Failure
X
X
–
This warning/fault is only active if the supply voltage to the
drive is less than the value set in
P 2.3.7 Power Loss Controller
Limit
, and
P 2.3.6 Power Loss Action
is NOT set to
[0] No Func-
tion
.
38
Internal Fault
–
X
X
Contact the local supplier.
40
Overload T15
X
–
–
Check the load connected to terminal 15 or remove short-cir-
cuit connection.
46
Gate drive Voltage
Fault
–
X
X
–
47
24 V Supply Low
X
X
X
24 V DC may be overloaded.
50
AMA calibration failed
–
X
–
A calibration error has occurred.
51
AMA check U
nom
and
I
nom
–
X
–
Wrong setting for motor voltage and/or motor current.
52
AMA low I
nom
–
X
–
Motor current is too low. Check the settings.
53
AMA big motor
–
X
–
The power size of the motor is too large for the AMA to oper-
ate.
54
AMA small motor
–
X
–
The power size of the motor is too small for the AMA to oper-
ate.
55
AMA parameter range
–
X
–
The parameter values of the motor are outside of the accept-
able range. AMA does not run.
56
AMA interrupt
–
X
–
The AMA is interrupted.
57
AMA timeout
–
X
–
–
58
AMA internal
–
X
–
Contact the local supplier.
59
Current Limit
X
X
–
The drive is overloaded.
60
External Interlock
–
X
–
External interlock has been activated.
61
Feedback Error
X
X
–
–
Danfoss A/S © 2024.03 AB413939445838en-000301 / 130R1254 |
263
Содержание iC2
Страница 1: ...iC2 Micro Frequency Converters Application Guide drives danfoss com...
Страница 2: ......
Страница 10: ...10 Danfoss A S 2024 03 AB413939445838en 000301 130R1254 Application Guide iC2 Micro Frequency Converters...
Страница 290: ...290 Danfoss A S 2024 03 AB413939445838en 000301 130R1254 Application Guide iC2 Micro Frequency Converters...
Страница 291: ......