Figure 40: Default Connections
1.
Set
P 5.4.1 Application Selection
to
[23] 3-Wire Control Mode
.
When
[23] 3-Wire Control Mode
is selected, the following parameters are automatically set to the values shown in the table.
Table 19: Default Settings
Category
Parameter index
Parameter name
Default setting
Parameter number
Operation mode
5.4.2
Operation Mode
[0] Speed Open Loop
100
DI 1 - T13
9.4.1.2
T13 Digital Input
[9] Latched start
510
DI 2 - T14
9.4.1.3
T14 Digital Input
[10] Reversing
511
DI/O - T15
9.4.1.4
T15 Digital Input
[1] Reset
512
DI 3 - T17
9.4.1.5
T17 Digital Input
[14] Jog
513
DI 4 - T18
9.4.1.6
T18 Digital Input
[6] Stop inverse
515
62
| Danfoss A/S © 2024.03 AB413939445838en-000301 / 130R1254
Application Guide | iC2-Micro Frequency Converters