PG8HRDW8 and PG9HRDW8 IQ

Hardwire PowerG Wired to Wireless

Converter Installation Manual

29011147R001

Summary of Contents for Tyco PowerG PG8HRDW8

Page 1: ... 29011147R001 PG8HRDW8 and PG9HRDW8 IQ Hardwire PowerG Wired to Wireless Converter Installation Manual 29011147R001 ...

Page 2: ...2 PG8HRDW8 and PG9HRDW8 IQ Hardwire PowerG Wired to Wireless Converter Installation Manual ...

Page 3: ...ing a keypad HSM2108 HSM2300 23 Enrolling the module 25 Testing the module placement 25 Enrolling wired zones automatically 26 Enrolling a keypad zone expander power supply 27 Attaching the cover 28 Status LEDs 29 Troubleshooting 30 Wiring diagram 31 FCC and ISED Canada Information 32 Modification statement 32 Interference statement 32 Wireless notice 32 FCC class B digital device notice 33 UL and...

Page 4: ...ational Warranty 39 Warranty Procedure 39 Conditions to Void Warranty 39 Items Not Covered by Warranty 39 Disclaimer of Warranties 40 Out of Warranty Repairs 40 Trademark 41 PG8HRDW8 and PG9HRDW8 IQ Hardwire PowerG Wired to Wireless Converter Installation Manual 4 ...

Page 5: ...al connections and damage to conductor insulation Instruct the user that there are no user serviceable parts in this equipment All equipment must be serviced by a skilled person Skilled persons are persons who have training or experience in the equipment technology particularly the various energies and energy magnitudes used in the equipment Skilled persons are expected to use their training and e...

Page 6: ...LC listed For UL and ULC installations use this device only in conjunction with compatible wireless receiver and control panel combinations model Qolsys IQPanel2 and IQPanel4 Before you begin make sure that the kit contains the following items The plastic enclosure containing the IQ Hardwire PowerG Wired to Wireless Converter The transformer The hardware pack The following table outlines panel com...

Page 7: ...level 9 6 VDC 2 PCB assembly current consumption 70 mA Standby battery Only use the battery rated 12 VDC 7 Ah The energy level of the battery when it is charged is 100 24 hour standby time and 5 minute alarm time for UL and ULC residential fire applications and ULC Security Level II applications Note The AUX current must not exceed 180 mA 24 hour standby time and 5 minute alarm time for UL and ULC...

Page 8: ... 5 VDC 50 mA PGM 2 voltage and current 11 3 VDC to 12 5 VDC 300 mA PG9HRDW8 Frequency band 912 75 MHz to 919 106 MHz Maximum power 0 0447 W RED BLK YEL GRN Corbus terminals used to provide power and communication between the converter and connected compatible modules Each compatible module keyapd expander power supply has four Corbus terminals that must be connected to the Corbus 11 3 VDC to 12 5 ...

Page 9: ...tional Electrical Code ANSI NFPA 70 the Standard for Installation and Classification of Burglar and Holdup Alarm Systems UL 681 and the Standard for Central Station Alarm Services UL 827 This module should be installed in accordance with Chapter 29 of the National Fire Alarm and Signaling Code ANSI NFPA 72 National Fire Protection Association Batterymarch Park Quincy MA 02269 Figure 1 Breakaway ta...

Page 10: ...e tamper screw to the wall For more information see Figure Mounting the power adapter You must mount the power adapter outside the PG8HRDW8 and PG9HRDW8 enclosure To mount the power adapter complete the following step Use two screws to secure the power adapter to the wall For more information see Callout 5 in Figure 2 Note Mount the power adapter close to an AC power outlet so there is no strain o...

Page 11: ...hen you connect to the PC Link make sure that the PCB side of the PC Link connector aligns with the white line on the module PCB and use only the four pins on the right 2 Wall tamper screw 3 Enrollment button 11 PG8HRDW8 and PG9HRDW8 IQ Hardwire PowerG Wired to Wireless Converter Installation Manual ...

Page 12: ...e end of line DEOL resistors Note For UL and ULC installations use only UL and ULC listed initiating devices that are compatible with the auxiliary output power range provided by the converter CAUTION Ensure the alarm controller is turned off before you wire the equipment When you wire zones observe the following guidelines For UL and ULC listed installations only use SEOL or DEOL connections Use ...

Page 13: ...d Secure Infinite Broken wire loop open Alarm Single end of line resistors You can use SEOL resistors to detect if a circuit is secure open or shorted Use this option if you use either normally closed or normally open devices You can configure SEOL supervision through zone programming on the control panel The following figure shows the different wiring configurations for SEOL resistors The image o...

Page 14: ...resistance of 100 Ω For more information see Table The following table shows the zone status for a given resistance value Table 6 SEOL zone status Resistance Description Status 0 Ω Shorted wire loop shorted Alarm 1 kΩ to 10 kΩ Contact closed Secure Infinite Broken wire loop open Alarm for burglary zones and Trouble for fire zones Double end of line resistors If you use DEOL resistors at the end of...

Page 15: ... 4 Normally closed contact Note Do not exceed a wire resistance of 100 Ω For more information see Table Note DEOL wiring is only for burglary use The following table shows the zone status for a given resistance value Table 7 DEOL zone status Resistance Description Status 0 Ω Shorted wire loop shorted Trouble 5600 Ω Contact closed Secure Infinite Broken wire loop open Tamper 11200 Ω Contact open Al...

Page 16: ...supply are required To wire the LED indicator see Figure 6 Figure 6 LED indicator wiring Callout Description 1 AUX terminals 2 PGM terminals 3 LED indicator 4 680 Ω resistor typical value To wire the relay output see Figure 7 PG8HRDW8 and PG9HRDW8 IQ Hardwire PowerG Wired to Wireless Converter Installation Manual 16 ...

Page 17: ... smoke detectors on a 2 wire loop Do not exceed a wire resistance of 24 Ω across the entire loop Do not use smoke detectors from different manufacturers on the same circuit as their operation may be impaired Refer to the smoke detector installation sheet when you position detectors For UL and ULC residential fire applications use only the AUX2 output to provide power to smoke and CO detectors If y...

Page 18: ...e information refer to the System Sensor installation manual Note Do not connect accessories such as a PRM 2W or any other polarity reversal module to 2 wire smoke detectors The UL compatibility ID for the FSA 210B series is FS200 and for the System Sensor models is A Note For ULC listed installations use FSA 210A series detectors or FSA 410A series detectors Note You must calculate and test the c...

Page 19: ...ire multiple CO detectors on the same loop you must break the leads between each CO detector You must power the supervision relay from the last detector in the loop If you use a non powered heat detector such as a fixed temperature or rate of rise type no supervision relay is required and you should not wire the detector to AUX2 or PGM2 To wire a 4 wire smoke heat or CO detector see the following ...

Page 20: ...ity the maximum AUX power load cannot exceed a current of 180 mA when using a 7 Ah battery Wiring the bell output You can use the BELL terminals to power a bell siren or other device which requires a steady output voltage when the system is in alarm The panel provides a current of up to 700 mA Note A 1 kΩ resistor is required across the BELL and BELL terminals or the system detects a trouble condi...

Page 21: ...e battery Wiring the module This section describes how to wire the external power supply and battery For more information see Figure 21 PG8HRDW8 and PG9HRDW8 IQ Hardwire PowerG Wired to Wireless Converter Installation Manual ...

Page 22: ...sitive terminals on the PCB and the battery 2 Connect the black battery lead to the negative terminals on the PCB and the battery Example Figure 12 Wiring the battery Important You must maintain a minimum separation of 6 4 mm 0 25 in at all points between non power limited battery wiring and all other power limited wiring connections Do not route any wiring over circuit boards You must maintain a ...

Page 23: ...e the keypad to perform the following operations To arm and disarm the system To view zone status To view partition status To use the keypad function keys The menus support 1 Bypass 2 Troubles 3 Alarm Memory 4 Chime 6 User Functions keypad buzzer contrast and brightness only 7 Command Outputs 1 4 9 No Entry Arm and 0 Quick Arm Quick Exit Note In v1 20 this is supported on up to 4x HSM2108 and 1 x ...

Page 24: ...nes are restored on system Figure 13 Keypad terminals Callout Description 1 R terminal 2 B terminal 3 Y terminal 4 G terminal 5 Not supported Example When you install multiple keypads and modules wire keypads using the same partition on the same module to improve keypad performance Keypads on partition one should be wired into module one and keypads on partition two should be wired into module two...

Page 25: ...t is a seven digit number that identifies the device being enrolled It has the format 460 XXXX Testing the module placement To test the signal strength between the module and the alarm panel complete the following steps Press the Enroll button on the module After the placement test is complete the color of the LED indicates the signal strength For more information see Table 11 Table 11 Device sign...

Page 26: ...the control panel The zones display on the control panel with the same ID as the module and zone label as the corresponding hardwired input Enable and configure each zone input and PGM using the zone configuration options on the control panel PG8HRDW8 and PG9HRDW8 IQ Hardwire PowerG Wired to Wireless Converter Installation Manual 26 ...

Page 27: ...roll all keypads and modules that are correctly wired to the module select Auto Learn b To manually enroll a keypad that is correctly wired to the module select Add Sensor Enter the module serial number 460 XXXX then select Corbus from the Hardwired Input drop down menu and enter the keypad or module serial number 27 PG8HRDW8 and PG9HRDW8 IQ Hardwire PowerG Wired to Wireless Converter Installation...

Page 28: ...over To attach the front cover to the enclosure follow the numbered steps in Figure 14 Example Figure 14 Attaching the cover PG8HRDW8 and PG9HRDW8 IQ Hardwire PowerG Wired to Wireless Converter Installation Manual 28 ...

Page 29: ...lashes every 120 ms if the firmware update fails Trouble The orange LED flashes twice every 10 seconds if any troubles are detected excluding a tamper trouble Note For detailed information on device troubles see the control panel Device enrollment The orange LED turns on when the enrollment button is pressed Device defaulting The red LED turns on if the enrollment button is pressed and held for 10...

Page 30: ... secured Zone fault Ensure that the zone is correctly wired and ensure that the zone EOL is correctly programmed Aux Short or overload There is a short or overload on the AUX terminals Low voltage The output voltage is below 9 8 VDC Low battery The battery voltage is below the low battery threshold of 11 5 VDC No battery There is no current detected on the battery terminals Fail to Enroll Press an...

Page 31: ...Wiring diagram For an overview of how to wire the system see the following figure Figure 15 Wiring diagram 31 PG8HRDW8 and PG9HRDW8 IQ Hardwire PowerG Wired to Wireless Converter Installation Manual ...

Page 32: ...anada applicables aux appareils radio exempts de licence L exploitation est autorisée aux deux conditions suivantes 1 l appareil ne doit pas produire de brouillage et 2 l utilisateur de l appareil doit accepter tout brouillage radioélectrique subi même si le brouillage est susceptible d en compromettre le fonctionnement Wireless notice This equipment complies with FCC and IC radiation exposure lim...

Page 33: ...an be determined by turning the equipment off and on the user is encouraged to try to correct the interference by one or more of the following measures Reorient or relocate the receiving antenna Increase the separation between the equipment and receiver Connect the equipment into an outlet on a circuit different from that to which the receiver is connected Consult the dealer or an experienced radi...

Page 34: ...ry shall be used to provide a minimum back up power of four hours as per specific application requirements UL and ULC household fire warning system Power supply model SOY 1800222 NA PGWLSHW40A or HS40WPSNA or HS40WPSAshall be employed 24 hour standby shall be provided At least one UL or ULC listed 4 wire latching type smoke detector rated to operate over the voltage range 11 3 VDC to 12 5 VDC A ma...

Page 35: ...onsidered outside the scope of the product s certification The Model PG8HRDW8 Wired to Wireless Converter has been certified by Telefication according to EN50131 1 2006 A1 2009 EN50131 3 2009 EN50131 5 3 2017 and EN50131 6 2017 Type A for Grade2 Class II Simplified EU declaration of conformity Hereby Tyco Safety Products Canada Ltd declares that the radio equipment type is in compliance with Direc...

Page 36: ...rnational copyright treaties as well as other intellectual property laws and treaties The SOFTWARE PRODUCT is licensed not sold 1 GRANT OF LICENSE This EULA grants You the following rights Software Installation and Use For each license You acquire You may have only one copy of the SOFTWARE PRODUCT installed Storage Network Use The SOFTWARE PRODUCT may not be installed accessed displayed run shared...

Page 37: ...WARE PRODUCT the accompanying printed materials and any copies of the SOFTWARE PRODUCT are owned by DSC or its suppliers You may not copy the printed materials accompanying the SOFTWARE PRODUCT All title and intellectual property rights in and to the content which may be accessed through use of the SOFTWARE PRODUCT are the property of the respective content owner and may be protected by applicable...

Page 38: ...THORIZES ANY OTHER PERSON PURPORTING TO ACT ON ITS BEHALF TO MODIFY OR TO CHANGE THIS WARRANTY NOR TO ASSUME FOR IT ANY OTHER WARRANTY OR LIABILITY CONCERNING THIS SOFTWARE PRODUCT EXCLUSIVE REMEDY AND LIMITATION OF WARRANTY UNDER NO CIRCUMSTANCES SHALL DSC BE LIABLE FOR ANY SPECIAL INCIDENTAL CONSEQUENTIAL OR INDIRECT DAMAGES BASED UPON BREACH OF WARRANTY BREACH OF CONTRACT NEGLIGENCE STRICT LIAB...

Page 39: ...onsible for any customs fees taxes or VAT that may be due Warranty Procedure To obtain service under this warranty please return the item s in question to the point of purchase All authorized distributors and dealers have a warranty program Anyone returning goods to Digital Security Controls must first obtain an authorization number Digital Security Controls will not accept any shipment whatsoever...

Page 40: ...rmitted by law Some states do not allow the exclusion or limitation of incidental or consequential damages so that the above may not apply to you Disclaimer of Warranties This warranty contains the entire warranty and shall be in lieu of any and all other warranties whether expressed or implied including all implied warranties of merchantability or fitness for a particular purpose and of all other...

Page 41: ...f their respective owners and are used with permission or allowed under applicable laws Product offerings and specifications are subject to change without notice Actual products may vary from photos Not all products include all features Availability varies by region contact your sales representative 2022 Johnson Controls All rights reserved JOHNSON CONTROLS TYCO and DSC are trademarks of Johnson C...