Default value:
0 [PNP]
Parameter type:
Selection
Parameter
number:
500
Unit:
–
Data type:
enum
Access type:
Read/Write
The following are the selections for the parameter.
Selection number
Selection name
Selection description
0
PNP
Action on positive directional pulses (0). PNP systems are pulled
down to ground (GND).
1
NPN
Action on negative directional pulses (1). NPN systems are pulled
up to +24 V internally in the frequency converter.
P 9.4.1.2 T13 Digital Input
Select the function from the available digital input range.
Default value:
8 [Start]
Parameter type:
Selection
Parameter
number:
510
Unit:
–
Data type:
enum
Access type:
Read/Write
The following are the selections for the parameter.
Selection number
Selection name
Selection description
0
No Operation
No reaction to signals transmitted to the terminal.
1
Reset
Resets the frequency converter after a trip/alarm. Not all alarms
can be reset.
2
Coast Inverse
Coasting stop, inverted input (NC). The frequency converter
leaves the motor in free mode. Logic 0
⇒
coasting stop.
3
Coast and Reset Inverse
Reset and coasting stop inverted input (NC). Leaves motor in free
mode and resets frequency converter. Logic 0
⇒
coasting stop.
Logic 1 to Logic 0
⇒
reset.
4
Quick Stop Inverse
Inverted input (NC). Generates a stop in accordance with the
quick stop ramp time set in
P 5.7.7 Quick Stop Ramp Time
. When
the motor stops, the shaft is in free mode. Logic 0
⇒
Quick-stop.
5
DC-brake Inverse
Inverted input for DC braking (NC). Stops the motor by
energizing it with a DC current for a certain time period. See
P
5.7.4 DC Brake Current %
to
P 5.7.5 DC Brake Frequency
. The
function is only active when the value in
P 5.7.3 DC Brake Time
is
different from 0. Logic 0
⇒
DC braking.
220
| Danfoss A/S © 2024.03 AB413939445838en-000301 / 130R1254
Application Guide | iC2-Micro Frequency Converters