Application Guide | iC2-Micro Frequency Converters
Selection number
Selection name
Selection description
6
Stop Inverse
Stop inverted function. Generates a stop function when the
selected terminal goes from logic 1 to logic 0. The stop is
performed according to the selected ramp time (
P 5.5.4.3 Ramp 1
Decel. Time
and
P 5.5.4.10 Ramp 2 Decel. Time
).
Note:
When the frequency converter is at the torque limit and
has received a stop command, it may not stop by itself. To ensure
that the frequency converter stops, configure a digital output to
[27] Torque limit
and stop and connect this digital output to a
digital input that is configured as coast.
8
Start
Select start for a start/stop command. Logic 1=start, logic 0=stop.
9
Latched Start
The motor starts when a pulse is applied for minimum 4 ms. The
motor stops when stop commands are given.
10
Reversing
Change the direction of motor shaft rotation. Select logic 1
to reverse. The reversing signal only changes the direction of
rotation. It does not activate the start function. Select both
directions in
P 5.8.1 Rotation Direction
. The function is not active
in process closed loop.
11
Start Reversing
Used for start/stop and for reversing on the same wire. Signals on
start are not allowed at the same time.
12
Enable Start Forward
Disengage the counterclockwise movement and allows for the
clockwise direction.
13
Enable Start Reverse
Disengage the clockwise movement and allows for the
counterclockwise direction.
14
Jog
Use to activate jog speed. See
P 5.9.2 Jog Reference 1
.
15
Preset Reference On
Shift between external reference and preset reference. It is
assumed that
[1] External/preset
has been selected in
P 5.5.3.5
Reference Function
. Logic 0 = external reference active; logic 1=1
of the preset references is active.
16
Preset Ref. Bit 0
Preset reference bits 0, 1, and 2 enable the selection of 1 of the 8
preset references. See
17
Preset Ref. Bit 1
Preset reference bits 0, 1, and 2 enable the selection of 1 of the 8
preset references. See
18
Preset Ref. Bit 2
Preset reference bits 0, 1, and 2 enable the selection of 1 of the 8
preset references. See
19
Freeze Reference
Freeze the actual reference, which is now the point of enable/
condition for
[21] Speed up
and
[22] Speed down
to be used.
If
[21] Speed up
or
[22] Speed down
is used, the speed change
always follows ramp 2 (
P 5.5.4.9 Ramp 2 Accel. Time
and
P 5.5.4.10
Ramp 2 Decel. Time
) in the range
P 5.5.3.3 Reference Maximum
.
Danfoss A/S © 2024.03 AB413939445838en-000301 / 130R1254 |
221
Содержание iC2
Страница 1: ...iC2 Micro Frequency Converters Application Guide drives danfoss com...
Страница 2: ......
Страница 10: ...10 Danfoss A S 2024 03 AB413939445838en 000301 130R1254 Application Guide iC2 Micro Frequency Converters...
Страница 290: ...290 Danfoss A S 2024 03 AB413939445838en 000301 130R1254 Application Guide iC2 Micro Frequency Converters...
Страница 291: ......