Application Guide | iC2-Micro Frequency Converters
Table 52: Lower Register Numbers for Input and Output Data
(continued)
02910 output data
Frequency converter status word register (STW)
02911 output data
Frequency converter main value register (MAV)
Speed ref.
CTW
Master-follower
e3
0b
a2
74
.1
1
15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0
Bit
no.:
Figure 65: Control Word According to FC Profile
Table 53: Control Word According to FC Profile
Bit
Bit value = 0
Bit value = 1
00
Reference value
External selection lsb
01
Reference value
External selection msb
02
DC brake
Ramp
03
Coasting
No coasting
04
Quick stop
Ramp
05
Hold output frequency
Use ramp
06
Ramp stop
Start
07
No function
Reset
08
No function
Jog
09
Ramp 1
Ramp 2
10
Data invalid
Data valid
11
Relay 01 open
Relay 01 active
12
Reserved
Reserved
13
Parameter setup
Selection lsb
14
Reserved
Reserved
15
No function
Reverse
6.1.8.2
Explanation of Control Word Bit
Bits 00/01
Bits 00 and 01 are used to select among the 4 reference values, which are preprogrammed in
P 5.5.3.10 Preset Reference
according to the
following table.
Danfoss A/S © 2024.03 AB413939445838en-000301 / 130R1254 |