Selection number
Selection name
Selection description
19
Freeze Reference
Freeze the actual reference, which is now the point of enable/
condition for
[21] Speed up
and
[22] Speed down
to be used.
If
[21] Speed up
or
[22] Speed down
is used, the speed change
always follows ramp 2 (
P 5.5.4.9 Ramp 2 Accel. Time
and
P
5.5.4.10 Ramp 2 Decel. Time
) in the range 0–
P 5.5.3.3 Reference
Maximum
.
20
Freeze Output
Freeze the actual motor frequency (Hz), which is now the point
of enable/condition for
[21] Speed up
and
[22] Speed down
to
be used. If
[21] Speed up
or
[22] Speed down
is used, the speed
change always follows ramp 2 (
P 5.5.4.9 Ramp 2 Accel. Time
and
P 5.5.4.10 Ramp 2 Decel. Time
) in the range 0–
P 4.2.2.4 Nominal
Frequency
.
Note:
When
[20] Freeze output
is active, the frequency converter
cannot be stopped by setting the signal on
[8] Start to low
.
Stop the frequency converter via a terminal programmed for
[2]
Coasting inverse
or
[3] Coast and reset, inverse
.
21
Speed Up
Select
[21] Speed up
and
[22] Speed down
if digital control of
the up/down speed is needed (motor potentiometer). Activate
this function by selecting either
[19] Freeze reference
or
[20]
Freeze output
. When speed up/down is activated for less than
400 ms, the resulting reference is increased/decreased by 0.1%. If
speed up/down is activated for more than 400 ms, the resulting
reference follows the setting in ramping up/down
P 5.5.4.9 Ramp
2 Accel. Time
/
P 5.5.4.10 Ramp 2 Decel. Time
. See
.
22
Speed Down
Select
[21] Speed up
and
[22] Speed down
if digital control of
the up/down speed is needed (motor potentiometer). Activate
this function by selecting either
[19] Freeze reference
or
[20]
Freeze output
. When speed up/down is activated for less than
400 ms, the resulting reference is increased/decreased by 0.1%. If
speed up/down is activated for more than 400 ms, the resulting
reference follows the setting in ramping up/down
P 5.5.4.9 Ramp
2 Accel. Time
/
P 5.5.4.10 Ramp 2 Decel. Time
. See
.
23
Set-up Select Bit 0
Select
[23] Set-up select bit 0
or
[1] Set-up select bit 1
to select 1
of the 2 set-ups. Set
P 6.6.1 Active Set-up
to
[9] Multi Set-up
.
25
Start and Coast
Select
[25] Start and Coast
for a start command or coast stop.
Logic 1=start, logic 0=coast stop.
28
Catch Up
Increase reference value by percentage (relative) set in
P 5.5.3.13
Freeze Up/Down Step Delta
. See
.
29
Slow Down
Reduce reference value by percentage (relative) set in
P 5.5.3.13
Freeze Up/Down Step Delta
. See
.
32
Pulse Input
The motor starts to run reverse when a pulse is applied for
minimum 4 ms. The motor stops when stop commands are
given.
34
Ramp bit 0
This function makes it possible to give an external fault to
the frequency converter. This fault is treated as an internally
generated alarm.
234
| Danfoss A/S © 2024.03 AB413939445838en-000301 / 130R1254
Application Guide | iC2-Micro Frequency Converters