Selection number
Selection name
Selection description
20
Freeze Output
Freeze the actual motor frequency (Hz), which is now the point
of enable/condition for
[21] Speed up
and
[22] Speed down
to
be used. If
[21] Speed up
or
[22] Speed down
is used, the speed
change always follows ramp 2 (
P 5.5.4.9 Ramp 2 Accel. Time
and
P 5.5.4.10 Ramp 2 Decel. Time
) in the range 0–
P 4.2.2.4 Nominal
Frequency
.
Note:
When
[20] Freeze output
is active, the frequency converter
cannot be stopped by setting the signal on
[8] Start to low
.
Stop the frequency converter via a terminal programmed for
[2]
Coasting inverse
or
[3] Coast and reset, inverse
.
21
Speed Up
Select
[21] Speed up
and
[22] Speed down
if digital control of
the up/down speed is needed (motor potentiometer). Activate
this function by selecting either
[19] Freeze reference
or
[20]
Freeze output
. When speed up/down is activated for less than
400 ms, the resulting reference is increased/decreased by 0.1%. If
speed up/down is activated for more than 400 ms, the resulting
reference follows the setting in ramping up/down
P 5.5.4.9 Ramp
2 Accel. Time
/
P 5.5.4.10 Ramp 2 Decel. Time
.
22
Speed Down
Select
[21] Speed up
and
[22] Speed down
if digital control of
the up/down speed is needed (motor potentiometer). Activate
this function by selecting either
[19] Freeze reference
or
[20]
Freeze output
. When speed up/down is activated for less than
400 ms, the resulting reference is increased/decreased by 0.1%. If
speed up/down is activated for more than 400 ms, the resulting
reference follows the setting in ramping up/down
P 5.5.4.9 Ramp
2 Accel. Time
/
P 5.5.4.10 Ramp 2 Decel. Time
.
23
Set-up Select Bit 0
Select
[23] Set-up select bit 0
to select 1 of the 2 set-ups. Set
P
6.6.1 Active Set-up
to
[9] Multi Set-up
.
25
Start and Coast
Select
[25] Start and Coast
for a start command or coast stop.
Logic 1=start, logic 0=coast stop.
28
Catch Up
Increase reference value by percentage (relative) set in
P 5.5.3.13
Freeze Up/Down Step Delta
. See
.
29
Slow Down
Reduce reference value by percentage (relative) set in
P 5.5.3.13
Freeze Up/Down Step Delta
. See
.
34
Ramp Bit 0
Enable a selection from the 2 ramps available.
45
Latched Start Reverse
The motor starts to run reverse when a pulse is applied for
minimum 4 ms. The motor stops when stop commands are
given.
51
External Interlock
This function makes it possible to give an external fault to
the frequency converter. This fault is treated as an internally
generated alarm.
60
Counter A (up)
Input for increment counting in the SLC counter A.
61
Counter A (down)
Input for decrement counting in the SLC counter A.
62
Reset Counter A
Input for reset of counter A.
222
| Danfoss A/S © 2024.03 AB413939445838en-000301 / 130R1254
Application Guide | iC2-Micro Frequency Converters
Содержание iC2
Страница 1: ...iC2 Micro Frequency Converters Application Guide drives danfoss com...
Страница 2: ......
Страница 10: ...10 Danfoss A S 2024 03 AB413939445838en 000301 130R1254 Application Guide iC2 Micro Frequency Converters...
Страница 290: ...290 Danfoss A S 2024 03 AB413939445838en 000301 130R1254 Application Guide iC2 Micro Frequency Converters...
Страница 291: ......