Add IP Solutions
Issue 7 November 2003
7-93
555-233-115
11. Affix the new TN802B label to the circuit pack.
12. Disconnect the monitor, keyboard, and mouse.
Circuit Pack Verification
1. Type change circuit-pack and press
Enter
.
2. Check the Code column to see if it says DSMAPD or MedPro.
.
3. To correct it, go to the entry just above the TN802B that says DSMAPD.
4. Type MEDPRO, and press
Enter
. Changing the one entry automatically
changes the entry above it. If it is in IP Trunk mode, you get the following
error message:
MedPro type requires TN802 with application. Type
MEDPRO on circuit-packs form.
5. To complete the administration, refer to the Administration for Network
Connectivity for Avaya Communication Manager book.
change circuit-packs Page 1 of 5
CIRCUIT PACKS
Cabinet: 1 Carrier: A
Carrier Type: processor
Slot Code Sf Mode Name Slot Code Sf Mode Name
11:
MEDPRO RESERVED-IP
01: TN754
DIGITAL LINE
12:
MEDPRO
RESERVED-IP
02: TN758
POOLED MODEM
13:
TN802 B
MAPD BOARD
03: TN2144
ANALOG LINE
14:
04: TN746 B
ANALOG LINE
15:
05
16:
06: TN771 C
MAINTENANCE/TEST
07: TN464 F
DS1 INTERFACE
08: TN2140
E&M TIE TRUNK
09: TN767 E
DS1 INTERFACE
10: TN799 B
CONTROL-LAN
’#’ indicates circuit pack conflict.