Table 63:
ZMRPSB (68) Group settings (advanced)
Name
Values (Range)
Unit
Step
Default
Description
tP1
0.000 - 60.000
s
0.001
0.045
Timer for detection of initial power swing
tP2
0.000 - 60.000
s
0.001
0.015
Timer for detection of subsequent power
swings
tW
0.000 - 60.000
s
0.001
0.250
Waiting timer for activation of tP2 timer
tH
0.000 - 60.000
s
0.001
0.500
Timer for holding power swing PICKUP output
tR1
0.000 - 60.000
s
0.001
0.300
Timer giving delay to inhibit by the residual
current
tR2
0.000 - 60.000
s
0.001
2.000
Timer giving delay to inhibit at very slow swing
Table 64:
ZMRPSB (68) Non group settings (basic)
Name
Values (Range)
Unit
Step
Default
Description
GlobalBaseSel
1 - 6
-
1
1
Selection of one of the Global Base Value
groups
6.7.6
Operation principle
Power swing detection (ZMRPSB ,68) function comprises an inner and an outer
quadrilateral measurement characteristic with load encroachment, as shown in figure
Its principle of operation is based on the measurement of the time it takes for a power
swing transient impedance to pass through the impedance area between the outer and the
inner characteristics. Power swings are identified by transition times longer than a
transition time set on corresponding timers. The impedance measuring principle is the
same as that used for the distance protection zones. The impedance and the characteristic
passing times are measured in all three phases separately.
1MRK 506 335-UUS A
Section 6
Impedance protection
177
Technical manual
Содержание REL650 series
Страница 1: ...Relion 650 series Line distance protection REL650 ANSI Technical manual ...
Страница 2: ......
Страница 42: ...36 ...
Страница 48: ...42 ...
Страница 58: ...52 ...
Страница 68: ...62 ...
Страница 74: ...68 ...
Страница 194: ...188 ...
Страница 534: ...528 ...
Страница 580: ...574 ...
Страница 722: ...716 ...
Страница 792: ...786 ...
Страница 855: ...849 ...