16.10
IEC 61850-8-1 redundant station bus communication
Function description
IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
System component for parallel
redundancy protocol
PRPSTATUS
-
-
16.10.1
Functionality
Redundant station bus communication according to IEC 62439-3 Edition 2 is available as
option in the Customized 650 Ver 1.3 series IEDs, and the selection is made at ordering.
Redundant station bus communication according to IEC 62439-3 Edition 2 uses both ports
LAN1A and LAN1B on the COM03 module.
Select COM03 for redundant station bus according to IEC 62439-3
Edition 2 protocol, at the time of ordering.
IEC 62439-3 Edition 2 is NOT compatible with IEC 62439-3 Edition 1.
16.10.2
Principle of operation
The redundant station bus communication is configured using the local HMI,
Main
Menu/Configuration/Communication/TCP-IP configuation/ETHLAN1_AB
. The
settings are also visible in PST in PCM600.
The communication is performed in parallel, that is the same data package is transmitted
on both channels simultaneously. The received package identity from one channel is
compared with the data package identity from the other channel. If the identity is the same,
the last package is discarded.
PRPSTATUS supervises redundant communication on the two channels. If no data
package has been received on one or both channels within the last 10 s, the output LAN1-
A and/or LAN1-B are set to indicate error.
Section 16
1MRK 506 335-UUS A
Station communication
734
Technical manual
Содержание REL650 series
Страница 1: ...Relion 650 series Line distance protection REL650 ANSI Technical manual ...
Страница 2: ......
Страница 42: ...36 ...
Страница 48: ...42 ...
Страница 58: ...52 ...
Страница 68: ...62 ...
Страница 74: ...68 ...
Страница 194: ...188 ...
Страница 534: ...528 ...
Страница 580: ...574 ...
Страница 722: ...716 ...
Страница 792: ...786 ...
Страница 855: ...849 ...