Table 257:
SXCBR Output signals
Name
Type
Description
XPOS
GROUP SIGNAL
Group connection to CSWI
EXE_OP
BOOLEAN
Executes the command for open direction
EXE_CL
BOOLEAN
Executes the command for close direction
OP_BLKD
BOOLEAN
Indication that the function is blocked for open
commands
CL_BLKD
BOOLEAN
Indication that the function is blocked for close
commands
UPD_BLKD
BOOLEAN
Update of position indication is blocked
POSITION
INTEGER
Apparatus position indication
OPENPOS
BOOLEAN
Apparatus open position
CLOSEPOS
BOOLEAN
Apparatus closed position
TR_POS
INTEGER
Truck position indication
CNT_VAL
INTEGER
Operation counter value
L_CAUSE
INTEGER
Latest value of the error indication during command
11.4.3.2
Settings
Table 258:
SXCBR Non group settings (basic)
Name
Values (Range)
Unit
Step
Default
Description
tStartMove
0.000 - 60.000
s
0.001
0.100
Supervision time for the apparatus to move
after a command
tIntermediate
0.000 - 60.000
s
0.001
0.150
Allowed time for intermediate position
AdaptivePulse
Not adaptive
Adaptive
-
-
Not adaptive
Output resets when a new correct end position
is reached
tOpenPulse
0.000 - 60.000
s
0.001
0.200
Output pulse length for open command
tClosePulse
0.000 - 60.000
s
0.001
0.200
Output pulse length for close command
SuppressMidPos
Disabled
Enabled
-
-
Enabled
Mid-position is suppressed during the time
tIntermediate
1MRK 506 335-UUS A
Section 11
Control
393
Technical manual
Содержание REL650 series
Страница 1: ...Relion 650 series Line distance protection REL650 ANSI Technical manual ...
Страница 2: ......
Страница 42: ...36 ...
Страница 48: ...42 ...
Страница 58: ...52 ...
Страница 68: ...62 ...
Страница 74: ...68 ...
Страница 194: ...188 ...
Страница 534: ...528 ...
Страница 580: ...574 ...
Страница 722: ...716 ...
Страница 792: ...786 ...
Страница 855: ...849 ...