![ABB REL650 series Скачать руководство пользователя страница 706](http://html.mh-extra.com/html/abb/rel650-series/rel650-series_technical-manual_4784706.webp)
14.22.2
Function block
IEC10000290-1-en.vsd
I103EF
BLOCK
51_EFFW
52_EFREV
IEC10000290 V1 EN
Figure 327:
I103EF function block
14.22.3
Signals
Table 521:
I103EF Input signals
Name
Type
Default
Description
BLOCK
BOOLEAN
0
Block of status reporting
51_EFFW
BOOLEAN
0
Information number 51, ground-fault forward
52_EFREV
BOOLEAN
0
Information number 52, ground-fault reverse
14.22.4
Settings
Table 522:
I103EF Non group settings (basic)
Name
Values (Range)
Unit
Step
Default
Description
FunctionType
1 - 255
-
1
160
Function type (1-255)
14.23
Function status fault protection for IEC 60870-5-103
I103FLTPROT
14.23.1
Functionality
I103FLTPROT is used for fault indications in monitor direction. Each input on the
function block is specific for a certain fault type and therefore must be connected to a
correspondent signal present in the configuration. For example: 68_TRGEN represents
the General Trip of the device, and therefore must be connected to the general trip signal
SMPPTRC_TRIP or equivalent.
The delay observed in the protocol is the time difference in between the signal that is
triggering the Disturbance Recorder and the respective configured signal to the IEC
60870-5-103 I103FLTPROT.
Section 14
1MRK 506 335-UUS A
Monitoring
700
Technical manual
Содержание REL650 series
Страница 1: ...Relion 650 series Line distance protection REL650 ANSI Technical manual ...
Страница 2: ......
Страница 42: ...36 ...
Страница 48: ...42 ...
Страница 58: ...52 ...
Страница 68: ...62 ...
Страница 74: ...68 ...
Страница 194: ...188 ...
Страница 534: ...528 ...
Страница 580: ...574 ...
Страница 722: ...716 ...
Страница 792: ...786 ...
Страница 855: ...849 ...