11.4.4
Circuit switch SXSWI
11.4.4.1
Signals
Table 259:
SXSWI Input signals
Name
Type
Default
Description
BLOCK
BOOLEAN
0
Block of function
LR_SWI
BOOLEAN
0
Local/Remote switch indication from switchyard
OPEN
BOOLEAN
0
Pulsed signal used to immediately open the switch
CLOSE
BOOLEAN
0
Pulsed signal used to immediately close the switch
BL_OPEN
BOOLEAN
0
Signal to block the open command
BL_CLOSE
BOOLEAN
0
Signal to block the close command
BL_UPD
BOOLEAN
0
Steady signal for block of the position updating
POSOPEN
BOOLEAN
0
Signal for open position of apparatus from I/O
POSCLOSE
BOOLEAN
0
Signal for close position of apparatus from I/O
TR_OPEN
BOOLEAN
0
Signal for open position of truck from I/O
TR_CLOSE
BOOLEAN
0
Signal for close position of truck from I/O
RS_CNT
BOOLEAN
0
Resets the operation counter
XIN
BOOLEAN
0
Execution information from CSWI
Table 260:
SXSWI Output signals
Name
Type
Description
XPOS
GROUP SIGNAL
Group connection to CSWI
EXE_OP
BOOLEAN
Executes the command for open direction
EXE_CL
BOOLEAN
Executes the command for close direction
OP_BLKD
BOOLEAN
Indication that the function is blocked for open
commands
CL_BLKD
BOOLEAN
Indication that the function is blocked for close
commands
UPD_BLKD
BOOLEAN
Update of position indication is blocked
POSITION
INTEGER
Apparatus position indication
OPENPOS
BOOLEAN
Apparatus open position
CLOSEPOS
BOOLEAN
Apparatus closed position
TR_POS
INTEGER
Truck position indication
CNT_VAL
INTEGER
Operation counter value
L_CAUSE
INTEGER
Latest value of the error indication during command
Section 11
1MRK 506 335-UUS A
Control
394
Technical manual
Содержание REL650 series
Страница 1: ...Relion 650 series Line distance protection REL650 ANSI Technical manual ...
Страница 2: ......
Страница 42: ...36 ...
Страница 48: ...42 ...
Страница 58: ...52 ...
Страница 68: ...62 ...
Страница 74: ...68 ...
Страница 194: ...188 ...
Страница 534: ...528 ...
Страница 580: ...574 ...
Страница 722: ...716 ...
Страница 792: ...786 ...
Страница 855: ...849 ...