AND
AND
AND
AND
AND
OR
OR
OR
a
b
a>b
AND
a
b
a>b
Pickup_BlKCont
AND
Time out A
BFP Started A
Reset A
52a_A
Current High A
Contact Closed A
ANSI09000977-2-en.vsd
FunctionMode
OR
OR
Current
Contact
Current and Contact
1
Pickup_PH
CB Closed A
I_A
ANSI09000977 V2 EN
Figure 122:
Simplified logic scheme of the CSPRBRF (50BF), CB position evaluation
200 ms
AND
AND
OR
OR
OR
TRRET_C
TRRET_B
BFP Started A
Retrip Time Out A
CB Closed A
TRRET
CB Pos Check
No CBPos Check
OR
From other
phases
ANSI16000504-1-en.vsd
RetripMode
1
30 ms
0
0-t1
TRRET_A
ANSI16000504 V1 EN
Figure 123:
Simplified logic scheme of the retrip logic function
Section 7
1MRK 506 335-UUS A
Current protection
266
Technical manual