[ ]
=
-
×
æ
ö
ç
÷
ç
÷
ç
÷
ç
÷
è
ø
0.339 0.235
td
t
s
Pickupn
i
EQUATION1647 V1 EN
(Equation 120)
where:
Pickupn is the set pickup current for step n
td
is set time multiplier for step n
i
is the measured current
The RD inverse curve gives a logarithmic delay, as used in the Combiflex protection
RXIDG. The curve enables a high degree of selectivity required for sensitive residual
ground-fault current protection, with ability to detect high-resistive ground faults. The
curve is described by equation
[ ]
=
-
×
×
æ
ö
ç
÷
è
ø
5.8 1.35 ln
i
t
td Pickupn
s
EQUATION1648 V1 EN
(Equation 121)
where:
Pickupn is the set pickup current for step n,
td
is set time multiplier for step n and
i
is the measured current
The timer will be reset directly when the current drops below the set pickup current level
minus the hysteresis.
21.3
Inverse time characteristics
When inverse time overcurrent characteristic is selected, the operate time
of the stage will be the sum of the inverse time delay and the set definite
time delay. Thus, if only the inverse time delay is required, it is of utmost
importance to set the definite time delay for that stage to zero.
1MRK 506 335-UUS A
Section 21
Time inverse characteristics
817
Technical manual
Содержание REL650 series
Страница 1: ...Relion 650 series Line distance protection REL650 ANSI Technical manual ...
Страница 2: ......
Страница 42: ...36 ...
Страница 48: ...42 ...
Страница 58: ...52 ...
Страница 68: ...62 ...
Страница 74: ...68 ...
Страница 194: ...188 ...
Страница 534: ...528 ...
Страница 580: ...574 ...
Страница 722: ...716 ...
Страница 792: ...786 ...
Страница 855: ...849 ...