Trip value rec
Fault locator
Sequential of
events
Event recorder
Indications
Disturbance
recorder
Disturbance Report
Binary signals
Analog signals
A4RADR
B6RBDR
DRPRDRE
FL
ANSI09000336-1-en.vsd
A1-4RADR
B1-6RBDR
ANSI09000336 V1 EN
Figure 298:
Disturbance report functions and related function blocks
The whole disturbance report can contain information for a number of recordings, each
with the data coming from all the parts mentioned above. The sequential of events
function is working continuously, independent of disturbance triggering, recording time,
and so on. All information in the disturbance report is stored in non-volatile flash
memories. This implies that no information is lost in case of loss of auxiliary power. Each
report will get an identification number in the interval from 0-999.
en05000125_ansi.vsd
Disturbance report
Record no. N
Record no. N+1
Record no. N+100
General dist.
information
Indications
Trip
values
Event
recordings
Disturbance
recording
Fault locator
Event list
(SOE)
ANSI05000125 V1 EN
Figure 299:
Disturbance report structure
Up to 100 disturbance reports can be stored. If a new disturbance is to be recorded when
the memory is full, the oldest disturbance report is overwritten by the new one. The total
recording capacity for the disturbance recorder is depending of sampling frequency,
1MRK 506 335-UUS A
Section 14
Monitoring
637
Technical manual
Содержание REL650 series
Страница 1: ...Relion 650 series Line distance protection REL650 ANSI Technical manual ...
Страница 2: ......
Страница 42: ...36 ...
Страница 48: ...42 ...
Страница 58: ...52 ...
Страница 68: ...62 ...
Страница 74: ...68 ...
Страница 194: ...188 ...
Страница 534: ...528 ...
Страница 580: ...574 ...
Страница 722: ...716 ...
Страница 792: ...786 ...
Страница 855: ...849 ...