17.16.2
Denial of service, frame rate control for front port DOSFRNT
17.16.2.1
Identification
Function description
IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
Denial of service, frame rate control for
front port
DOSFRNT
-
-
17.16.2.2
Function block
DOSFRNT
LINKUP
WARNING
ALARM
IEC09000133-1-en.vsd
IEC09000133 V1 EN
Figure 360:
DOSFRNT function block
17.16.2.3
Signals
Table 608:
DOSFRNT Output signals
Name
Type
Description
LINKUP
BOOLEAN
Ethernet link status
WARNING
BOOLEAN
Frame rate is higher than normal state
ALARM
BOOLEAN
Frame rate is higher than throttle state
17.16.2.4
Settings
The function does not have any parameters available in the local HMI or PCM600.
Section 17
1MRK 506 335-UUS A
Basic IED functions
782
Technical manual