Name
Type
Description
I1RANG
INTEGER
I1Amplitude range
I1ANGL
REAL
I1 Angle
I2
REAL
I2 Amplitude
I2RANG
INTEGER
I2 Magnitude range
I2ANGL
REAL
I2Angle
14.1.5.4
Settings
Table 437:
CMSQI Non group settings (basic)
Name
Values (Range)
Unit
Step
Default
Description
Operation
Disabled
Enabled
-
-
Disabled
Operation Disable / Enable
3I0DbRepInt
1 - 300
Type
1
10
Cycl: Report interval (s), Db: In % of range, Int
Db: In %s
3I0Min
0 - 500000
A
1
0
Minimum value
3I0Max
0 - 500000
A
1
3300
Maximum value
3I0RepTyp
Cyclic
Dead band
Int deadband
-
-
Dead band
Reporting type
3I0LimHys
0.000 - 100.000
%
0.001
5.000
Hysteresis value in % of range and is common
for all limits
3I0AngDbRepInt
1 - 300
Type
1
10
Cycl: Report interval (s), Db: In % of range, Int
Db: In %s
I1DbRepInt
1 - 300
Type
1
10
Cycl: Report interval (s), Db: In % of range, Int
Db: In %s
I1Min
0 - 500000
A
1
0
Minimum value
I1Max
0 - 500000
A
1
1300
Maximum value
I1RepTyp
Cyclic
Dead band
Int deadband
-
-
Dead band
Reporting type
I1AngDbRepInt
1 - 300
Type
1
10
Cycl: Report interval (s), Db: In % of range, Int
Db: In %s
I2DbRepInt
1 - 300
Type
1
10
Cycl: Report interval (s), Db: In % of range, Int
Db: In %s
I2Min
0 - 500000
A
1
0
Minimum value
I2Max
0 - 500000
A
1
1300
Maximum value
I2RepTyp
Cyclic
Dead band
Int deadband
-
-
Dead band
Reporting type
I2LimHys
0.000 - 100.000
%
0.001
5.000
Hysteresis value in % of range and is common
for all limits
I2AngDbRepInt
1 - 300
Type
1
10
Cycl: Report interval (s), Db: In % of range, Int
Db: In %s
Section 14
1MRK 506 335-UUS A
Monitoring
588
Technical manual
Содержание REL650 series
Страница 1: ...Relion 650 series Line distance protection REL650 ANSI Technical manual ...
Страница 2: ......
Страница 42: ...36 ...
Страница 48: ...42 ...
Страница 58: ...52 ...
Страница 68: ...62 ...
Страница 74: ...68 ...
Страница 194: ...188 ...
Страница 534: ...528 ...
Страница 580: ...574 ...
Страница 722: ...716 ...
Страница 792: ...786 ...
Страница 855: ...849 ...