13.4.1.4
PULSETIMER function block
Identification
Function description
IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
PULSETIMER function block
PULSETIMER
-
-
Functionality
The pulse function can be used, for example for pulse extensions or limiting of operation
of outputs. The PULSETIMER has a settable length.
Function block
PULSETIMER
INPUT
OUT
IEC09000291-1-en.vsd
IEC09000291 V1 EN
Figure 263:
PULSETIMER function block
Signals
Table 379:
PULSETIMER Input signals
Name
Type
Default
Description
INPUT
BOOLEAN
0
Input signal
Table 380:
PULSETIMER Output signals
Name
Type
Description
OUT
BOOLEAN
Output signal
Settings
Table 381:
PULSETIMER Non group settings (basic)
Name
Values (Range)
Unit
Step
Default
Description
t
0.000 - 90000.000
s
0.001
0.010
Pulse time length
Section 13
1MRK 506 335-UUS A
Logic
546
Technical manual