EQUATION97 V1 EN
(Equation 103)
Thus, the general fault location equation for a single line is:
FA
A
A
L
F
A
I
V
I p Z
R
D
= × ×
+
×
EQUATION1596 V1 EN
(Equation 104)
Table 494:
Expressions for V
A
, I
A
and I
FA
for different types of faults
Fault type:
V
A
I
A
I
FA
AG
V
AA
I
AA
+ K
N
x I
NA
(
)
AA
0 A
3
2
I
I
× D
-
EQUATION1597 V1 EN
BG
V
BA
I
BA
+ K
N
x I
NA
(
)
BA
0 A
3
2
I
I
× D
-
EQUATION1598 V1 EN
CG
V
CA
I
CA
+ K
N
x I
NA
(
)
CA
0 A
3
2
I
I
× D
-
EQUATION1599 V1 EN
ABC, AB, ABG
V
AA
-V
BA
I
AA
- I
BA
D
I
ABA
BC, BCG
V
BA
-V
CA
I
BA
- I
CA
D
I
CBA
CA, CAG
V
CA
-V
AA
I
CA
- I
AA
D
I
CAA
The K
N
complex quantity for zero-sequence compensation for the single line is equal to:
K
N
Z
0L
Z
1L
–
3 Z
1L
×
------------------------
=
EQUATION99 V1 EN
(Equation 105)
D
I is the change in current, that is the current after the fault minus the current before the
fault.
In the following, the positive sequence impedance for Z
A
, Z
B
and Z
L
is inserted into the
equations, because this is the value used in the algorithm.
For double lines, the fault equation is:
Section 14
1MRK 506 335-UUS A
Monitoring
668
Technical manual
Содержание REL650 series
Страница 1: ...Relion 650 series Line distance protection REL650 ANSI Technical manual ...
Страница 2: ......
Страница 42: ...36 ...
Страница 48: ...42 ...
Страница 58: ...52 ...
Страница 68: ...62 ...
Страница 74: ...68 ...
Страница 194: ...188 ...
Страница 534: ...528 ...
Страница 580: ...574 ...
Страница 722: ...716 ...
Страница 792: ...786 ...
Страница 855: ...849 ...