AND
OR
AND
S
AND
AND
OR
ANSI09000203-2-en.vsd
initiate
block start
UnsucClByCBchk = CBcheck
UNSUCCL
shot 0
Pulse SMBRREC
(Closing)
52a
CBclosed
R
0
0-tUnsucCl
ANSI09000203 V2 EN
Figure 174:
Issue of signal UNSUCCL, unsuccessful reclosing
Automatic continuation of the reclosing sequence
The auto-reclosing function can be programmed to proceed to the following reclosing
shots (if selected) even if the initiate signals are not received from the protection functions,
but the breaker is still not closed. This is done by setting parameter
AutoCont
=
Enabled
and to the required delay for the function to proceed without a new initiate.
AND
AND
AND
OR
OR
RI
52a
initiate
en05000787_ansi.vsd
CLOSECMD
S
R
Q
CBClosed
0
0-tAutoContWait
ANSI05000787 V1 EN
Figure 175:
Automatic proceeding of shot 2 to 5
1MRK 506 335-UUS A
Section 11
Control
373
Technical manual
Содержание REL650 series
Страница 1: ...Relion 650 series Line distance protection REL650 ANSI Technical manual ...
Страница 2: ......
Страница 42: ...36 ...
Страница 48: ...42 ...
Страница 58: ...52 ...
Страница 68: ...62 ...
Страница 74: ...68 ...
Страница 194: ...188 ...
Страница 534: ...528 ...
Страница 580: ...574 ...
Страница 722: ...716 ...
Страница 792: ...786 ...
Страница 855: ...849 ...