10.2.7.3
Dead line detection
A simplified diagram for the functionality is found in figure
. A dead phase condition
is indicated if both the voltage and the current in one phase is below their respective setting
values
VDLDPU
and
IDLDPU
. If at least one phase is considered to be dead the output
DLD1PH and the internal signal DeadLineDet1Ph is activated. If all three phases are
considered to be dead the output DLD3PH is activated
IA
IB
IC
a
b
a<b
a
b
a<b
a
b
a<b
IDLDPU
VA
VB
VC
a
b
a<b
a
b
a<b
a
b
a<b
VDLDPU
OR
AND
AND
AND
AND
AND
AND
AND
AllCurrLow
DeadLineDet1Ph
DLD3PH
DLD1PH
intBlock
Dead Line Detection
ANSI0000035-1-en.vsd
ANSI0000035 V1 EN
Figure 160:
Simplified logic diagram for Dead Line detection part
10.2.7.4
Main logic
A simplified diagram for the functionality is found in figure
. The fuse failure
supervision function (SDDRFUF) can be switched on or off by the setting parameter
Operation
to
Enabled
or
Disabled
.
For increased flexibility and adaptation to system requirements an operation mode
selector,
OpModeSel
, has been introduced to make it possible to select different operating
modes for the negative and zero sequence based algorithms. The different operation
modes are:
•
Disabled
. The negative and zero sequence function is disabled.
•
V2I2
. Negative sequence is selected.
•
V0I0
. Zero sequence is selected.
Section 10
1MRK 506 335-UUS A
Secondary system supervision
340
Technical manual
Содержание REL650 series
Страница 1: ...Relion 650 series Line distance protection REL650 ANSI Technical manual ...
Страница 2: ......
Страница 42: ...36 ...
Страница 48: ...42 ...
Страница 58: ...52 ...
Страница 68: ...62 ...
Страница 74: ...68 ...
Страница 194: ...188 ...
Страница 534: ...528 ...
Страница 580: ...574 ...
Страница 722: ...716 ...
Страница 792: ...786 ...
Страница 855: ...849 ...