Name
Values (Range)
Unit
Step
Default
Description
CTprim4
1 - 99999
A
1
1000
Rated CT primary current
VTsec5
0.001 - 999.999
V
0.001
110.000
Rated VT secondary voltage
VTprim5
0.001 - 9999.999
kV
0.001
132.000
Rated VT primary voltage
VTsec6
0.001 - 999.999
V
0.001
110
Rated VT secondary voltage
VTprim6
0.001 - 9999.999
kV
0.001
132
Rated VT primary voltage
VTsec7
0.001 - 999.999
V
0.001
110.000
Rated VT secondary voltage
VTprim7
0.001 - 9999.999
kV
0.001
132.000
Rated VT primary voltage
VTsec8
0.001 - 999.999
V
0.001
110
Rated VT secondary voltage
VTprim8
0.001 - 9999.999
kV
0.001
132
Rated VT primary voltage
VTsec9
0.001 - 999.999
V
0.001
110.000
Rated VT secondary voltage
VTprim9
0.001 - 9999.999
kV
0.001
132.000
Rated VT primary voltage
VTsec10
0.001 - 999.999
V
0.001
110
Rated VT secondary voltage
VTprim10
0.001 - 9999.999
kV
0.001
132
Rated VT primary voltage
Table 6:
AIM_6I_4U Non group settings (basic)
Name
Values (Range)
Unit
Step
Default
Description
CTStarPoint1
FromObject
ToObject
-
-
ToObject
ToObject= towards protected object,
FromObject= the opposite
CTsec1
0.1 - 10.0
A
0.1
1
Rated CT secondary current
CTprim1
1 - 99999
A
1
1000
Rated CT primary current
CTStarPoint2
FromObject
ToObject
-
-
ToObject
ToObject= towards protected object,
FromObject= the opposite
CTsec2
0.1 - 10.0
A
0.1
1.0
Rated CT secondary current
CTprim2
1 - 99999
A
1
1000
Rated CT primary current
CTStarPoint3
FromObject
ToObject
-
-
ToObject
ToObject= towards protected object,
FromObject= the opposite
CTsec3
0.1 - 10.0
A
0.1
1
Rated CT secondary current
CTprim3
1 - 99999
A
1
1000
Rated CT primary current
CTStarPoint4
FromObject
ToObject
-
-
ToObject
ToObject= towards protected object,
FromObject= the opposite
CTsec4
0.1 - 10.0
A
0.1
1.0
Rated CT secondary current
CTprim4
1 - 99999
A
1
1000
Rated CT primary current
CTStarPoint5
FromObject
ToObject
-
-
ToObject
ToObject= towards protected object,
FromObject= the opposite
CTsec5
0.1 - 10.0
A
0.1
1
Rated CT secondary current
CTprim5
1 - 99999
A
1
1000
Rated CT primary current
CTStarPoint6
FromObject
ToObject
-
-
ToObject
ToObject= towards protected object,
FromObject= the opposite
Table continues on next page
1MRK 506 335-UUS A
Section 3
Analog inputs
59
Technical manual
Содержание REL650 series
Страница 1: ...Relion 650 series Line distance protection REL650 ANSI Technical manual ...
Страница 2: ......
Страница 42: ...36 ...
Страница 48: ...42 ...
Страница 58: ...52 ...
Страница 68: ...62 ...
Страница 74: ...68 ...
Страница 194: ...188 ...
Страница 534: ...528 ...
Страница 580: ...574 ...
Страница 722: ...716 ...
Страница 792: ...786 ...
Страница 855: ...849 ...