Name
Values (Range)
Unit
Step
Default
Description
AlarmTemp
0 - 200
Deg C
1
80
Temperature level for pickup (alarm)
TripTemp
0 - 300
Deg C
1
90
Temperature level for trip
ReclTemp
0 - 300
Deg C
1
75
Temperature for reset of lockout after trip
AmbiSens
Disabled
Enabled
-
-
Disabled
External temperature sensor available
DefaultAmbTemp
-50 - 100
Deg C
1
20
Ambient temperature used when AmbiSens is
set to Off
DefaultTemp
-50 - 300
Deg C
1
50
Temperature raise above ambient temperature
at startup
Table 127:
LCPTTR (26) Non group settings (basic)
Name
Values (Range)
Unit
Step
Default
Description
GlobalBaseSel
1 - 6
-
1
1
Selection of one of the Global Base Value
groups
7.9.6
Monitored data
Table 128:
LFPTTR (26) Monitored data
Name
Type
Values (Range)
Unit
Description
TTRIP
INTEGER
-
-
Estimated time to trip (in min)
TENRECL
INTEGER
-
-
Estimated time to reset of
lockout (in min)
TEMP
REAL
-
Temperature
Fahrenheit
Calculated temperature of the
device
TEMPAMB
REAL
-
Temperature
Fahrenheit
Ambient temperature used in
the calculations
Table 129:
LCPTTR (26) Monitored data
Name
Type
Values (Range)
Unit
Description
TTRIP
INTEGER
-
-
Estimated time to trip (in min)
TENRECL
INTEGER
-
-
Estimated time to reset of
lockout (in min)
TEMP
REAL
-
deg
Calculated temperature of the
device
TEMPAMB
REAL
-
deg
Ambient temperature used in
the calculations
Section 7
1MRK 506 335-UUS A
Current protection
252
Technical manual
Содержание REL650 series
Страница 1: ...Relion 650 series Line distance protection REL650 ANSI Technical manual ...
Страница 2: ......
Страница 42: ...36 ...
Страница 48: ...42 ...
Страница 58: ...52 ...
Страница 68: ...62 ...
Страница 74: ...68 ...
Страница 194: ...188 ...
Страница 534: ...528 ...
Страница 580: ...574 ...
Страница 722: ...716 ...
Страница 792: ...786 ...
Страница 855: ...849 ...