6.3.3
Function block
ANSI09000154-1-en.vsd
FMPSPDIS
I3P*
V3P*
BLOCK
ZPICK UP
TR3PH
PICKUP
PU_A
PU_B
PU_C
PHG_FLT
PHSCND
DLECND
PU_BLF
ANSI09000154 V1 EN
Figure 66:
FMPSPDIS (21) function block
6.3.4
Signals
Table 37:
FMPSPDIS Input signals
Name
Type
Default
Description
I3P
GROUP
SIGNAL
-
Three phase group signal for current inputs
V3P
GROUP
SIGNAL
-
Three phase group signal for voltage inputs
BLOCK
BOOLEAN
0
Block of function
Zpick up
BOOLEAN
0
Pick up from under impedance function
TR3PH
BOOLEAN
0
Three phase tripping initiated
Table 38:
FMPSPDIS Output signals
Name
Type
Description
PICKUP
BOOLEAN
General pickup signal
PU_A
BOOLEAN
Fault detected in phase A
PU_B
BOOLEAN
Fault detected in phase B
PU_C
BOOLEAN
Fault detected in phase C
PHG_FLT
BOOLEAN
Ground fault detected
PHSCND
INTEGER
Binary coded starts from phase selection
DLECND
INTEGER
Binary coded starts from load encroachment only
PU_BLF
INTEGER
Binary coded starts from fund. frequency based blinders
Section 6
1MRK 506 335-UUS A
Impedance protection
148
Technical manual
Содержание REL650 series
Страница 1: ...Relion 650 series Line distance protection REL650 ANSI Technical manual ...
Страница 2: ......
Страница 42: ...36 ...
Страница 48: ...42 ...
Страница 58: ...52 ...
Страница 68: ...62 ...
Страница 74: ...68 ...
Страница 194: ...188 ...
Страница 534: ...528 ...
Страница 580: ...574 ...
Страница 722: ...716 ...
Страница 792: ...786 ...
Страница 855: ...849 ...