Name of input
Type
Default
Description
Value when
activated
Value when
deactivated
IN7
BOOLEAN
0
Input 7
64
0
IN8
BOOLEAN
0
Input 8
128
0
IN9
BOOLEAN
0
Input 9
256
0
IN10
BOOLEAN
0
Input 10
512
0
IN11
BOOLEAN
0
Input 11
1024
0
IN12
BOOLEAN
0
Input 12
2048
0
IN13
BOOLEAN
0
Input 13
4096
0
IN14
BOOLEAN
0
Input 14
8192
0
IN15
BOOLEAN
0
Input 15
16384
0
IN16
BOOLEAN
0
Input 16
32768
0
The sum of the numbers in column “Value when activated” when all INx (where 1≤x≤16)
are active that is=1; is 65535. 65535 is the highest boolean value that can be converted to
an integer by the B16I function block.
13.7
Boolean 16 to integer conversion with logic node
representation B16IFCVI
13.7.1
Identification
Function description
IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
Boolean 16 to integer conversion with
logic node representation
B16IFCVI
-
-
13.7.2
Functionality
Boolean 16 to integer conversion with logic node representation function B16IFCVI is
used to transform a set of 16 binary (logical) signals into an integer. The block input will
freeze the output at the last value.
Section 13
1MRK 506 335-UUS A
Logic
560
Technical manual
Содержание REL650 series
Страница 1: ...Relion 650 series Line distance protection REL650 ANSI Technical manual ...
Страница 2: ......
Страница 42: ...36 ...
Страница 48: ...42 ...
Страница 58: ...52 ...
Страница 68: ...62 ...
Страница 74: ...68 ...
Страница 194: ...188 ...
Страница 534: ...528 ...
Страница 580: ...574 ...
Страница 722: ...716 ...
Страница 792: ...786 ...
Страница 855: ...849 ...