Name
Values (Range)
Unit
Step
Default
Description
PDbRepInt
1 - 300
Type
1
10
Cycl: Report interval (s), Db: In % of range, Int
Db: In %s
PZeroDb
0 - 100000
m%
1
500
Zero point clamping
PHiLim
-2000.0 - 2000.0
%SB
0.1
120.0
High limit in % of SBase
PLowLim
-2000.0 - 2000.0
%SB
0.1
-120.0
Low limit in % of SBase
PLowLowLim
-2000.0 - 2000.0
%SB
0.1
-150.0
Low Low limit in % of SBase
PLimHyst
0.000 - 100.000
%
0.001
5.000
Hysteresis value in % of range (common for all
limits)
QDbRepInt
1 - 300
Type
1
10
Cycl: Report interval (s), Db: In % of range, Int
Db: In %s
QZeroDb
0 - 100000
m%
1
500
Zero point clamping
QHiHiLim
-2000.0 - 2000.0
%SB
0.1
150.0
High High limit in % of SBase
QHiLim
-2000.0 - 2000.0
%SB
0.1
120.0
High limit in % of SBase
QLowLim
-2000.0 - 2000.0
%SB
0.1
-120.0
Low limit in % of SBase
QLowLowLim
-2000.0 - 2000.0
%SB
0.1
-150.0
Low Low limit in % of SBase
QLimHyst
0.000 - 100.000
%
0.001
5.000
Hysteresis value in % of range (common for all
limits)
UGenZeroDb
1 - 100
%VB
1
5
Zero point clamping in % of VBase
PFDbRepInt
1 - 300
Type
1
10
Cycl: Report interval (s), Db: In % of range, Int
Db: In %s
PFZeroDb
0 - 100000
m%
1
500
Zero point clamping
IGenZeroDb
1 - 100
%IB
1
5
Zero point clamping in % of IBase
PFHiHiLim
-1.000 - 1.000
-
0.001
1.000
High High limit (physical value)
PFHiLim
-1.000 - 1.000
-
0.001
0.800
High limit (physical value)
PFLowLim
-1.000 - 1.000
-
0.001
-0.800
Low limit (physical value)
PFLowLowLim
-1.000 - 1.000
-
0.001
-1.000
Low Low limit (physical value)
PFLimHyst
0.000 - 100.000
%
0.001
5.000
Hysteresis value in % of range (common for all
limits)
UDbRepInt
1 - 300
Type
1
10
Cycl: Report interval (s), Db: In % of range, Int
Db: In %s
UZeroDb
0 - 100000
m%
1
500
Zero point clamping
UHiHiLim
0.0 - 200.0
%VB
0.1
150.0
High High limit in % of UBase
UHiLim
0.0 - 200.0
%VB
0.1
120.0
High limit in % of VBase
ULowLim
0.0 - 200.0
%VB
0.1
80.0
Low limit in % of VBase
ULowLowLim
0.0 - 200.0
%VB
0.1
60.0
Low Low limit in % of VBase
ULimHyst
0.000 - 100.000
%
0.001
5.000
Hysteresis value in % of range (common for all
limits)
IDbRepInt
1 - 300
Type
1
10
Cycl: Report interval (s), Db: In % of range, Int
Db: In %s
IZeroDb
0 - 100000
m%
1
500
Zero point clamping
Table continues on next page
Section 14
1MRK 506 335-UUS A
Monitoring
580
Technical manual
Содержание REL650 series
Страница 1: ...Relion 650 series Line distance protection REL650 ANSI Technical manual ...
Страница 2: ......
Страница 42: ...36 ...
Страница 48: ...42 ...
Страница 58: ...52 ...
Страница 68: ...62 ...
Страница 74: ...68 ...
Страница 194: ...188 ...
Страница 534: ...528 ...
Страница 580: ...574 ...
Страница 722: ...716 ...
Страница 792: ...786 ...
Страница 855: ...849 ...