15.2.4
Signals
Table 536:
ETPMMTR Input signals
Name
Type
Default
Description
P
REAL
0
Measured active power
Q
REAL
0
Measured reactive power
STACC
BOOLEAN
0
Start to accumulate energy values
RSTACC
BOOLEAN
0
Reset of accumulated enery reading
RSTDMD
BOOLEAN
0
Reset of maximum demand reading
Table 537:
ETPMMTR Output signals
Name
Type
Description
ACCST
BOOLEAN
Start of accumulating energy values
EAFPULSE
BOOLEAN
Accumulated forward active energy pulse
EARPULSE
BOOLEAN
Accumulated reverse active energy pulse
ERFPULSE
BOOLEAN
Accumulated forward reactive energy pulse
ERRPULSE
BOOLEAN
Accumulated reverse reactive energy pulse
EAFALM
BOOLEAN
Alarm for active forward energy exceed limit in set
interval
EARALM
BOOLEAN
Alarm for active reverse energy exceed limit in set
interval
ERFALM
BOOLEAN
Alarm for reactive forward energy exceed limit in set
interval
ERRALM
BOOLEAN
Alarm for reactive reverse energy exceed limit in set
interval
EAFACC
REAL
Accumulated forward active energy value
EARACC
REAL
Accumulated reverse active energy value
ERFACC
REAL
Accumulated forward reactive energy value
ERRACC
REAL
Accumulated reverse reactive energy value
MAXPAFD
REAL
Maximum forward active power demand value for set
interval
MAXPARD
REAL
Maximum reverse active power demand value for set
interval
MAXPRFD
REAL
Maximum forward reactive power demand value for set
interval
MAXPRRD
REAL
Maximum reactive power demand value in reverse
direction
Section 15
1MRK 506 335-UUS A
Metering
712
Technical manual
Содержание REL650 series
Страница 1: ...Relion 650 series Line distance protection REL650 ANSI Technical manual ...
Страница 2: ......
Страница 42: ...36 ...
Страница 48: ...42 ...
Страница 58: ...52 ...
Страница 68: ...62 ...
Страница 74: ...68 ...
Страница 194: ...188 ...
Страница 534: ...528 ...
Страница 580: ...574 ...
Страница 722: ...716 ...
Страница 792: ...786 ...
Страница 855: ...849 ...