Description
Type test value
Reference
Power frequency (50 Hz)
magnetic field
IEC 61000-4-8, level 5
•
3 s
1000 A/m
•
Continuous
100 A/m
Pulse magnetic field immunity
test
1000A/m
IEC 61000–4–9, level 5
Damped oscillatory magnetic
field
100A/m, 100 kHz and 1MHz
IEC 6100–4–10, level 5
Power frequency immunity test
IEC 60255-22-7, class A
IEC 61000-4-16
•
Common mode
300 V rms
•
Differential mode
150 V rms
Voltage dips and short
interruptionsc on DC power
supply
Dips:
40%/200 ms
70%/500 ms
Interruptions:
0-50 ms: No restart
0...∞ s : Correct behaviour at
power down
IEC 60255-11
IEC 61000-4-11
Voltage dips and interruptions on
AC power supply
Dips:
40% 10/12 cycles at 50/60 Hz
70% 25/30 cycles at 50/60 Hz
Interruptions:
0–50 ms: No restart
0...∞ s: Correct behaviour at power
down
IEC 60255–11
IEC 61000–4–11
Electromagnetic emission tests
EN 55011, class A
IEC 60255-25
ANSI C63.4, FCC
•
Conducted, RF-emission
(mains terminal)
0.15...0.50 MHz
< 79 dB(µV) quasi peak
< 66 dB(µV) average
0.5...30 MHz
< 73 dB(µV) quasi peak
< 60 dB(µV) average
•
Radiated RF-emission,
ANSI
30 – 88 MHz
< 39,08 dB(µV/m) quasi peak,
measured at 10 m distance
Table continues on next page
Section 20
1MRK 506 335-UUS A
IED and functionality tests
808
Technical manual
Содержание REL650 series
Страница 1: ...Relion 650 series Line distance protection REL650 ANSI Technical manual ...
Страница 2: ......
Страница 42: ...36 ...
Страница 48: ...42 ...
Страница 58: ...52 ...
Страница 68: ...62 ...
Страница 74: ...68 ...
Страница 194: ...188 ...
Страница 534: ...528 ...
Страница 580: ...574 ...
Страница 722: ...716 ...
Страница 792: ...786 ...
Страница 855: ...849 ...