Table 86:
OC4PTOC (51_67) Group settings (advanced)
Name
Values (Range)
Unit
Step
Default
Description
HarmRestrain
Disabled
Enabled
-
-
Disabled
Enable block from harmonic restrain
2ndHarmStab
5 - 100
%IFund
1
20
Pickup of second harm restraint in % of
Fundamental
HarmRestrain1
Disabled
Enabled
-
-
Disabled
Enable block of step 1 from harmonic restrain
HarmRestrain2
Disabled
Enabled
-
-
Disabled
Enable block of step 2 from harmonic restrain
HarmRestrain3
Disabled
Enabled
-
-
Disabled
Enable block of step3 from harmonic restrain
HarmRestrain4
Disabled
Enabled
-
-
Disabled
Enable block of step 4 from harmonic restrain
Table 87:
OC4PTOC (51_67) Non group settings (basic)
Name
Values (Range)
Unit
Step
Default
Description
GlobalBaseSel
1 - 6
-
1
1
Selection of one of the Global Base Value
groups
MeasType
DFT
RMS
-
-
DFT
Selection between DFT and RMS
measurement
7.3.6
Monitored data
Table 88:
OC4PTOC (51_67) Monitored data
Name
Type
Values (Range)
Unit
Description
DIRL1
INTEGER
1=Forward
2=Reverse
0=No direction
-
Direction for phase A
DIRL2
INTEGER
1=Forward
2=Reverse
0=No direction
-
Direction for phase B
DIRL3
INTEGER
1=Forward
2=Reverse
0=No direction
-
Direction for phase C
IL1
REAL
-
A
Current in phase A
IL2
REAL
-
A
Current in phase B
IL3
REAL
-
A
Current in phase C
7.3.7
Operation principle
The protection design can be divided in four parts:
Section 7
1MRK 506 335-UUS A
Current protection
198
Technical manual
Содержание REL650 series
Страница 1: ...Relion 650 series Line distance protection REL650 ANSI Technical manual ...
Страница 2: ......
Страница 42: ...36 ...
Страница 48: ...42 ...
Страница 58: ...52 ...
Страница 68: ...62 ...
Страница 74: ...68 ...
Страница 194: ...188 ...
Страница 534: ...528 ...
Страница 580: ...574 ...
Страница 722: ...716 ...
Страница 792: ...786 ...
Страница 855: ...849 ...