Figure 307:
Fault on transmission line fed from both ends
From figure
= × ×
+ ×
A
A
L
F
F
V
I p Z
I R
EQUATION1595 V1 EN
(Equation 101)
Where:
I
A
is the line current after the fault, that is, pre-fault current plus current change due to the fault,
I
F
is the fault current and
p
is a relative distance to the fault
The fault current is expressed in measurable quantities by:
I
F
I
FA
D
A
--------
=
EQUATION96 V1 EN
(Equation 102)
Where:
I
FA
is the change in current at the point of measurement, IED A and
D
A
is a fault current-distribution factor, that is, the ratio between the fault current at line end A and the
total fault current.
For a single line, the value is equal to:
1MRK 506 335-UUS A
Section 14
Monitoring
667
Technical manual