14.15.9
Technical data
Table 501:
SPVNZBAT Technical data
Function
Range or value
Accuracy
Lower limit for the battery terminal
voltage
(60-140) % of Vbat
± 1.0% of set battery voltage
Reset ratio, lower limit
<105 %
-
Upper limit for the battery terminal
voltage
(60-140) % of Vbat
± 1.0% of set battery voltage
Reset ratio, upper limit
>95 %
-
Timers
(0.000-60.000) s
± 0.5% ± 110 ms
Battery rated voltage
20-250V
-
14.16
Insulation gas monitoring function SSIMG (63)
14.16.1
Identification
Function description
IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
Insulation gas monitoring function
SSIMG
-
63
14.16.2
Functionality
Insulation gas monitoring function SSIMG (63) is used for monitoring the circuit breaker
condition. Binary information based on the gas pressure in the circuit breaker is used as
input signals to the function. In addition, the function generates alarms based on received
information.
14.16.3
Function block
ANSI09000129-1-en.vsd
SSIMG (63)
BLOCK
BLK_ALM
PRESSURE
TEMP
PRES_ALM
PRES_LO
SET_P_LO
SET_T_LO
RESET_LO
PRESSURE
PRES_ALM
PRES_LO
TEMP
TEMP_ALM
TEMP_LO
ANSI09000129 V1 EN
Figure 310:
SSIMG (63) function block
1MRK 506 335-UUS A
Section 14
Monitoring
675
Technical manual
Содержание REL650 series
Страница 1: ...Relion 650 series Line distance protection REL650 ANSI Technical manual ...
Страница 2: ......
Страница 42: ...36 ...
Страница 48: ...42 ...
Страница 58: ...52 ...
Страница 68: ...62 ...
Страница 74: ...68 ...
Страница 194: ...188 ...
Страница 534: ...528 ...
Страница 580: ...574 ...
Страница 722: ...716 ...
Страница 792: ...786 ...
Страница 855: ...849 ...