14.18.2
Functionality
The circuit breaker condition monitoring function SSCBR is used to monitor different
parameters of the circuit breaker. The breaker requires maintenance when the number of
operations has reached a predefined value. For proper functioning of the circuit breaker,
it is essential to monitor the circuit breaker operation, spring charge indication, breaker
wear, travel time, number of operation cycles and accumulated energy. The energy is
calculated from the measured input currents as a sum of I
^
2 t values. Alarms are generated
when the calculated values exceed the threshold settings.
The function contains a block alarm functionality.
The supervised and presented breaker functions include
•
breaker open and close travel time
•
spring charging time
•
number of breaker operations
•
accumulated I
Y
t per phase with alarm and lockout
•
remaining breaker life per phase
•
breaker inactivity
14.18.3
Function block
ANSI10000281-1-en.vsd
SSCBR
I3P*
BLOCK
BLK_ALM
POSOPEN
POSCLOSE
ALMPRES
LOPRES
SPRCHRGN
SPRCHRGD
CBCNTRST
IACCRST
SPCHTRST
TRVTRST
TRVTOAL
TRVTCAL
SPRCHRAL
OPRALM
OPRLOALM
IACCALM
IACCLOAL
CBLIFEAL
NOOPRALM
PRESALM
PRESLO
CBOPEN
CBINVPOS
52a
ANSI10000281 V1 EN
Figure 312:
SSCBR function block
1MRK 506 335-UUS A
Section 14
Monitoring
681
Technical manual
Содержание REL650 series
Страница 1: ...Relion 650 series Line distance protection REL650 ANSI Technical manual ...
Страница 2: ......
Страница 42: ...36 ...
Страница 48: ...42 ...
Страница 58: ...52 ...
Страница 68: ...62 ...
Страница 74: ...68 ...
Страница 194: ...188 ...
Страница 534: ...528 ...
Страница 580: ...574 ...
Страница 722: ...716 ...
Страница 792: ...786 ...
Страница 855: ...849 ...