15.1.4
Signals
Table 531:
PCGGIO Input signals
Name
Type
Default
Description
BLOCK
BOOLEAN
0
Block of function
READ_VAL
BOOLEAN
0
Initiates an additional pulse counter reading
BI_PULSE
BOOLEAN
0
Connect binary input channel for metering
RS_CNT
BOOLEAN
0
Resets pulse counter value
Table 532:
PCGGIO Output signals
Name
Type
Description
INVALID
BOOLEAN
The pulse counter value is invalid
RESTART
BOOLEAN
The reported value does not comprise a complete
integration cycle
BLOCKED
BOOLEAN
The pulse counter function is blocked
NEW_VAL
BOOLEAN
A new pulse counter value is generated
SCAL_VAL
REAL
Scaled value with time and status information
15.1.5
Settings
Table 533:
PCGGIO Non group settings (basic)
Name
Values (Range)
Unit
Step
Default
Description
Operation
Off
On
-
-
Off
Operation Off/On
EventMask
NoEvents
ReportEvents
-
-
NoEvents
Report mask for analog events from pulse
counter
CountCriteria
Off
RisingEdge
Falling edge
OnChange
-
-
RisingEdge
Pulse counter criteria
Scale
1.000 - 90000.000
-
0.001
1.000
Scaling value for SCAL_VAL output to unit per
counted value
Quantity
Count
ActivePower
ApparentPower
ReactivePower
ActiveEnergy
ApparentEnergy
ReactiveEnergy
-
-
Count
Measured quantity for SCAL_VAL output
tReporting
1 - 3600
s
1
60
Cycle time for reporting of counter value
Section 15
1MRK 506 335-UUS A
Metering
708
Technical manual
Содержание REL650 series
Страница 1: ...Relion 650 series Line distance protection REL650 ANSI Technical manual ...
Страница 2: ......
Страница 42: ...36 ...
Страница 48: ...42 ...
Страница 58: ...52 ...
Страница 68: ...62 ...
Страница 74: ...68 ...
Страница 194: ...188 ...
Страница 534: ...528 ...
Страница 580: ...574 ...
Страница 722: ...716 ...
Страница 792: ...786 ...
Страница 855: ...849 ...