Name
Type
Default
Description
CSUR
BOOLEAN
0
Signal to be used for channel start with underreaching
pilot schemes
CR
BOOLEAN
0
Channel receive input signal from communications
apparatus/module for pilot communication scheme logic
CR_GUARD
BOOLEAN
0
Carrier channel guard input signal
Table 353:
ECPSCH (85) Output signals
Name
Type
Description
TRIP
BOOLEAN
Trip by pilot communication scheme logic
CS
BOOLEAN
Pilot channel start signal
CRL
BOOLEAN
Channel receive signal output from communication
scheme logic
LCG
BOOLEAN
Loss of channel guard signal output from
communication scheme logic
12.5.5
Settings
Table 354:
ECPSCH (85) Group settings (basic)
Name
Values (Range)
Unit
Step
Default
Description
Operation
Disabled
Enabled
-
-
Disabled
Disable/Enable Operation
SchemeType
Disabled
Intertrip
Permissive UR
Permissive OR
Blocking
-
-
Permissive UR
Scheme type, Mode of Operation
tCoord
0.000 - 60.000
s
0.001
0.035
Communication scheme channel coordination
time
tSendMin
0.000 - 60.000
s
0.001
0.100
Minimum duration of a carrier send signal
(carrier continuation)
Table 355:
ECPSCH (85) Group settings (advanced)
Name
Values (Range)
Unit
Step
Default
Description
Unblock
Disabled
NoRestart
Restart
-
-
Disabled
Operation mode of unblocking logic
tSecurity
0.000 - 60.000
s
0.001
0.035
Security timer for loss of carrier guard detection
Section 12
1MRK 506 335-UUS A
Scheme communication
518
Technical manual
Содержание REL650 series
Страница 1: ...Relion 650 series Line distance protection REL650 ANSI Technical manual ...
Страница 2: ......
Страница 42: ...36 ...
Страница 48: ...42 ...
Страница 58: ...52 ...
Страница 68: ...62 ...
Страница 74: ...68 ...
Страница 194: ...188 ...
Страница 534: ...528 ...
Страница 580: ...574 ...
Страница 722: ...716 ...
Страница 792: ...786 ...
Страница 855: ...849 ...